Analysis of Capacitor Unbalance Protection activation due to AC filter tripping incident at ±660kV HVDC Lahore converter station

This study examines an AC filter tripping incident that occurred at Lahore Converter station of ±660kV high voltage direct current (HVDC) Pak Matiari-Lahore transmission project which seriously affected the stable operation of the converter station. The fault current exceeded the trip threshold and lasted for more than 20 milliseconds, causing the activation of capacitor unbalance protection. The short circuit discharge phenomenon occurring between the layers of the capacitors is responsible for tripping the filter leading to the activation of capacitor unbalance protection. The incident emphasizes how important protection methods are to maintaining system stability in unusual circumstances. The fault mechanism is thoroughly examined, including its underlying causes and modes of transmission. In order to prevent the expensive equipment from damage, the study highlights the importance of precise protective settings. To reduce future dangers, suggestions are made for better operation and maintenance procedures and cutting-edge monitoring systems. By taking these measures, the AC filter's robustness and dependability will be improved, especially during difficult grid circumstances like periods of high demand.

Authors

Publication Details

Journal
Journal of Engineering Research and Reviews.
Published
2025-01-01
DOI
https://doi.org/10.5455/jerr.20250102040226
Primary Topic
High-Voltage Power Transmission Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of Capacitor Unbalance Protection activation due to AC filter tripping incident at ±660kV HVDC Lahore converter station

A. Naveed, Habib Ullah, Muhammad Ali Imran, Mohammad Shehzad et al.
Journal of Engineering Research and Reviews.
High-Voltage Power Transmission Systems
article

Analysis of Capacitor Unbalance Protection activation due to AC filter tripping incident at ±660kV HVDC Lahore converter station

A. Naveed, Habib Ullah, Muhammad Ali Imran, Mohammad Shehzad, zhang jianmeng
article en

Abstract

This study examines an AC filter tripping incident that occurred at Lahore Converter station of ±660kV high voltage direct current (HVDC) Pak Matiari-Lahore transmission project which seriously affected the stable operation of the converter station. The fault current exceeded the trip threshold and lasted for more than 20 milliseconds, causing the activation of capacitor unbalance protection. The short circuit discharge phenomenon occurring between the layers of the capacitors is responsible for tripping the filter leading to the activation of capacitor unbalance protection. The incident emphasizes how important protection methods are to maintaining system stability in unusual circumstances. The fault mechanism is thoroughly examined, including its underlying causes and modes of transmission. In order to prevent the expensive equipment from damage, the study highlights the importance of precise protective settings. To reduce future dangers, suggestions are made for better operation and maintenance procedures and cutting-edge monitoring systems. By taking these measures, the AC filter's robustness and dependability will be improved, especially during difficult grid circumstances like periods of high demand.

Journal of Engineering Research and Reviews.(0)
Openalex Percentile: Top 95%
High-Voltage Power Transmission Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.