Method for Detection and Limitation of Short-Circuit Currents for Semiconductor Circuit Breakers in LVDC Grids Using a Pre-Saturated Inductor
This paper introduces an innovative non-destructive device designed to detect and limit short-circuit currents in LVDC grids. The proposed solution utilizes a transformer fully saturated by a permanent magnet during normal operation. When a short-circuit condition occurs, the transformer desaturates, reducing the rise in current and triggering the detection and protection mechanism. The structure and functionality of the device, along with the design criteria, are discussed. Additionally, optimization measures are presented, examined, and validated. Experimental results from the advanced device prototype demonstrate its effectiveness in detecting and limiting overcurrents. The device features a stable tripping threshold and can safely and reliably interrupt even low time constant capacitive short-circuits. This hardware-based detection solution is ideally suited for installation in a semiconductor circuit breaker.
Authors
- Raffael Schwanninger
- Vincent Lorentz
- Johannes Gehring
- Bernd Wunder (ORCID: https://orcid.org/0009-0007-3543-4158)
- Martin Maerz (ORCID: https://orcid.org/0000-0003-2444-0484)
- Alexander Nowak
Institutions
- Fraunhofer Institute for Integrated Systems and Device Technology (DE)
- University of Bayreuth (DE)
Publication Details
- Journal
- IEEE Open Journal of Power Electronics
- Published
- 2025-01-01
- DOI
- https://doi.org/10.1109/ojpel.2025.3555797
- Citations
- 4
- Primary Topic
- High-Voltage Power Transmission Systems
- Type
- article
- Field-Weighted Citation Impact
- 2.92