Data-Light Oscillation Mode Identification for Fast Stability Assessment of Grid-Tied Converters
Dynamic mode decomposition (DMD) is an effective data-driven oscillation mode identification method for instability identification in grid-tied converters. However, time-consuming computation and empirical setting of parameters limit its practical application in rapid stability assessment. This article introduces data-light dynamic mode decomposition (DL-DMD) by integrating the conventional dynamic mode decomposition (DMD) algorithm with harmonic state space theory, which significantly improves computational speed while providing a bandwidth-oriented interpretation for parameter selection in correspondence with the identifiable frequency range of modes. The effectiveness and advantages of the proposed method are verified through offline analysis and online tests based on an experimental platform.
Authors
- Guoqing Gao (ORCID: https://orcid.org/0000-0002-4123-3121)
- Xiangyu Meng (ORCID: https://orcid.org/0000-0002-8886-1408)
- Frede Blaabjerg (ORCID: https://orcid.org/0000-0001-8311-7412)
- Rui Kong (ORCID: https://orcid.org/0009-0003-2602-0616)
- Shuyu Ou (ORCID: https://orcid.org/0000-0002-6339-6984)
- Subham Sahoo (ORCID: https://orcid.org/0000-0002-7916-028X)
Institutions
- Southwest Jiaotong University (CN)
- Aalborg University (DK)
Publication Details
- Journal
- IEEE Transactions on Power Electronics
- Published
- 2025-03-31
- DOI
- https://doi.org/10.1109/tpel.2025.3556387
- Primary Topic
- Power Systems and Renewable Energy
- Type
- article
- Field-Weighted Citation Impact
- 0.00
Funders
- European Commission