This paper investigates air leakage rates between the common corridor and the lift shaft within modern high-rise residential buildings via the lift doors. A literature review has been undertaken which indicates that leakage areas for lift doors are suggested as being between 0.047 and 0.060 m 2 with only the latest version of BS EN 12101-13:2022 indicating that a reduction may be necessary to 0.020 m 2 for more modern buildings. Leakage areas have been investigated for a 22 storey residential building by recording on-site flowrate and pressure measurements whilst a lift car is in operation as well as attempting to measure the gaps across a set of lift doors. The maximum instantaneous flowrate measured was −89 L/s into the shaft and +99 L/s out of the shaft. The largest pressure change recorded was a depressurisation of −22.5 Pa and the highest pressure recorded was +19.5 Pa. These values result in a maximum calculated leakage area of 0.020 m 2 for this building. This value is approximately half of the lift leakage area previously quoted in BS EN 12101-6:2005, however is closer to the suggested tight lift door value of 0.020 m 2 in BS EN 12101-13:2020 and would indicate that these are more appropriate for use in analyses of modern buildings. Practical application When undertaking computational fluid dynamics (CFD) modelling of smoke control systems within the common corridors of residential buildings, leakage values can be used for lift doors based on values quoted in BS EN 12101-13:2022. For a pressurisation system design, it is more onerous to use larger values, however, when designing a mechanical extract or depressurisation system, a lower leakage rate is potentially more onerous. This paper shows that the use of lower lift door leakage values from the standard as being more appropriate for use as input conditions within CFD simulations.

Authors

Publication Details

Journal
Building Services Engineering Research and Technology
Published
2025-03-29
DOI
https://doi.org/10.1177/01436244251325223
Primary Topic
Elevator Systems and Control
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Measuring lift door air leakage rates in modern high-rise residential buildings

Michael Spearpoint, A.P.L. Turner, Andrew Basford
Building Services Engineering Research and Technology
Elevator Systems and Control
article

Measuring lift door air leakage rates in modern high-rise residential buildings

Michael Spearpoint, A.P.L. Turner, Andrew Basford
article en

Abstract

This paper investigates air leakage rates between the common corridor and the lift shaft within modern high-rise residential buildings via the lift doors. A literature review has been undertaken which indicates that leakage areas for lift doors are suggested as being between 0.047 and 0.060 m 2 with only the latest version of BS EN 12101-13:2022 indicating that a reduction may be necessary to 0.020 m 2 for more modern buildings. Leakage areas have been investigated for a 22 storey residential building by recording on-site flowrate and pressure measurements whilst a lift car is in operation as well as attempting to measure the gaps across a set of lift doors. The maximum instantaneous flowrate measured was −89 L/s into the shaft and +99 L/s out of the shaft. The largest pressure change recorded was a depressurisation of −22.5 Pa and the highest pressure recorded was +19.5 Pa. These values result in a maximum calculated leakage area of 0.020 m 2 for this building. This value is approximately half of the lift leakage area previously quoted in BS EN 12101-6:2005, however is closer to the suggested tight lift door value of 0.020 m 2 in BS EN 12101-13:2020 and would indicate that these are more appropriate for use in analyses of modern buildings. Practical application When undertaking computational fluid dynamics (CFD) modelling of smoke control systems within the common corridors of residential buildings, leakage values can be used for lift doors based on values quoted in BS EN 12101-13:2022. For a pressurisation system design, it is more onerous to use larger values, however, when designing a mechanical extract or depressurisation system, a lower leakage rate is potentially more onerous. This paper shows that the use of lower lift door leakage values from the standard as being more appropriate for use as input conditions within CFD simulations.

Building Services Engineering Research and TechnologyVol. 46(4)
Openalex Percentile: Top 94%
Elevator Systems and Control
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.