Implementation of a Virtualized PMU in a CPC Platform Based on IEC61850 Sampled Values

This article presents the implementation of phasor measurement units (PMUs) using IEC61850 sampled values (SVs) in a centralized protection and control (CPC) platform called EPICS platform. The SV-PMU microservice is developed and implemented via software on an EDGE Server. Two versions of the SV-PMU microservice were implemented and evaluated, the first one uses a two-cycle finite impulse response (FIR) filter, and the second one uses a one-cycle FIR filter. Both implementations use the signals generated by a stand-alone merging unit (SAMU) as input. The SV-PMU microservice performance is evaluated in the laboratory in both steady and transient states according to IEEE/IEC 60255-118-1:2018 standard. The evaluation tests were executed using a real-time digital simulator (RTDS). Two methods for the evaluation of the behavior of the PMUs in terms of total vector error (TVE), frequency error (FE), and RFE were implemented. The tests results demonstrate the microservice’s compliance with the synchrophasor standards requirements in terms of TVE, FE, RFE, and latency. Future improvements are required to warrantee the TVE values during 10% rated current magnitude test. This implementation enhances the EPICS platform’s capabilities as a CPC system in digital substations and to contribute to the deployment of wide area monitoring, protection, and control (WAMPAC) systems in the power grid. This work includes the comparison of the behavior of SV-PMU microservice with a commercial PMU to validate its real-world applicability.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Instrumentation and Measurement
Published
2025-01-01
DOI
https://doi.org/10.1109/tim.2025.3555681
Citations
1
Primary Topic
Smart Grid Security and Resilience
Type
article
Field-Weighted Citation Impact
1.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Implementation of a Virtualized PMU in a CPC Platform Based on IEC61850 Sampled Values

Maria Teresa Villén Martínez, Aníbal Antonio Prada Hurtado, M. Mañana, M. A. Oliván et al.
1 citations
IEEE Transactions on Instrumentation and Measurement
Smart Grid Security and Resilience
1.21
article

Implementation of a Virtualized PMU in a CPC Platform Based on IEC61850 Sampled Values

Maria Teresa Villén Martínez, Aníbal Antonio Prada Hurtado, M. Mañana, M. A. Oliván, Carlos Rodriguez del Castillo, Eduardo Martínez Carrasco
article en
1 citations

Abstract

This article presents the implementation of phasor measurement units (PMUs) using IEC61850 sampled values (SVs) in a centralized protection and control (CPC) platform called EPICS platform. The SV-PMU microservice is developed and implemented via software on an EDGE Server. Two versions of the SV-PMU microservice were implemented and evaluated, the first one uses a two-cycle finite impulse response (FIR) filter, and the second one uses a one-cycle FIR filter. Both implementations use the signals generated by a stand-alone merging unit (SAMU) as input. The SV-PMU microservice performance is evaluated in the laboratory in both steady and transient states according to IEEE/IEC 60255-118-1:2018 standard. The evaluation tests were executed using a real-time digital simulator (RTDS). Two methods for the evaluation of the behavior of the PMUs in terms of total vector error (TVE), frequency error (FE), and RFE were implemented. The tests results demonstrate the microservice’s compliance with the synchrophasor standards requirements in terms of TVE, FE, RFE, and latency. Future improvements are required to warrantee the TVE values during 10% rated current magnitude test. This implementation enhances the EPICS platform’s capabilities as a CPC system in digital substations and to contribute to the deployment of wide area monitoring, protection, and control (WAMPAC) systems in the power grid. This work includes the comparison of the behavior of SV-PMU microservice with a commercial PMU to validate its real-world applicability.

IEEE Transactions on Instrumentation and MeasurementVol. 74
Universidad de Cantabria (ES), Red Electrica de Espana (Spain) (ES), CIRCE - Centro Tecnológico (ES)
Openalex Percentile: Top 23%
Smart Grid Security and Resilience
1.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.