A Cascaded Power Frequency Overvoltage During Joint Alternating Current Fault Ride-Though at Sending End Among Islanding Wind Farms and their Voltage Source Converter-Based High Voltage Direct Current Integration Systems via Simulation

In this paper, a cascaded power frequency overvoltage is reported during joint alternating current (AC) fault ride-though among islanding wind farms and the Voltage Source Converter-Based High Voltage Direct Current (VSC-HVDC) integration systems via simulation. It is found that the wind power is divided into two different batches of overvoltage off-grid at two adjacent moments, and the corresponding mechanism has been found. Then, the cascaded mechanism and explanation has been verified by several elaborate validations. Also, the technical measure has been proposed to avoid such cascaded power frequency overvoltage, which includes adopting VSC-HVDC with better overcurrent capacity, and installing synchronous condenser in islanding wind farms. Finally, these technical measures have been fully validated by numerical illustrations.

Authors

Institutions

Publication Details

Published
2024-12-27
DOI
https://doi.org/10.1109/ic2ecs64405.2024.10928708
Primary Topic
Islanding Detection in Power Systems
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A Cascaded Power Frequency Overvoltage During Joint Alternating Current Fault Ride-Though at Sending End Among Islanding Wind Farms and their Voltage Source Converter-Based High Voltage Direct Current Integration Systems via Simulation

Naixin Duan, Yilang Jiang, Xiaoqiang Sun, Meng Wang et al.
Islanding Detection in Power Systems
article

A Cascaded Power Frequency Overvoltage During Joint Alternating Current Fault Ride-Though at Sending End Among Islanding Wind Farms and their Voltage Source Converter-Based High Voltage Direct Current Integration Systems via Simulation

Naixin Duan, Yilang Jiang, Xiaoqiang Sun, Meng Wang, Nan Yang, Yingying Wang, Qinghai Li
article en

Abstract

In this paper, a cascaded power frequency overvoltage is reported during joint alternating current (AC) fault ride-though among islanding wind farms and the Voltage Source Converter-Based High Voltage Direct Current (VSC-HVDC) integration systems via simulation. It is found that the wind power is divided into two different batches of overvoltage off-grid at two adjacent moments, and the corresponding mechanism has been found. Then, the cascaded mechanism and explanation has been verified by several elaborate validations. Also, the technical measure has been proposed to avoid such cascaded power frequency overvoltage, which includes adopting VSC-HVDC with better overcurrent capacity, and installing synchronous condenser in islanding wind farms. Finally, these technical measures have been fully validated by numerical illustrations.

North China Electric Power University (CN), State Grid Corporation of China (China) (CN), China Electric Power Research Institute
State Grid Corporation of China
Affordable and clean energy
Openalex Percentile: Top 73%
Islanding Detection in Power Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.