An Improved PLL-Based Control Technique for Seamless Transition Between Grid-Connected and Islanding Modes

This paper proposes an improved practical phase-locked loop (PLL) based control with minimum PI Controllers for a seamless transition between grid-connected and islanding modes and vice versa for an AC microgrid. The developed controls are suitable for converters in droop control mode of operation in islanded mode and grid following control mode for grid-connected mode. Further, it also addresses issues of transients on connected load during the initialization of the island to the grid synchronization process. A detailed design approach for developed controls is presented. The proposed system controls have been verified by simulation studies and validated for Control hardware in a loop system consisting of one 500 kW Grid Forming converter and a 500 kW Grid Following Converter operating in parallel.

Authors

Institutions

Publication Details

Published
2024-09-26
DOI
https://doi.org/10.1109/icpeev63032.2024.10932018
Citations
1
Primary Topic
Islanding Detection in Power Systems
Type
article
Field-Weighted Citation Impact
0.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

An Improved PLL-Based Control Technique for Seamless Transition Between Grid-Connected and Islanding Modes

Shoubhik Mukherjee, Anshu Priya, Mukesh Kumar Pathak, Deepak Gehlot et al.
1 citations
Islanding Detection in Power Systems
0.21
article

An Improved PLL-Based Control Technique for Seamless Transition Between Grid-Connected and Islanding Modes

Shoubhik Mukherjee, Anshu Priya, Mukesh Kumar Pathak, Deepak Gehlot, E. Nageswara Rao
article en
1 citations

Abstract

This paper proposes an improved practical phase-locked loop (PLL) based control with minimum PI Controllers for a seamless transition between grid-connected and islanding modes and vice versa for an AC microgrid. The developed controls are suitable for converters in droop control mode of operation in islanded mode and grid following control mode for grid-connected mode. Further, it also addresses issues of transients on connected load during the initialization of the island to the grid synchronization process. A detailed design approach for developed controls is presented. The proposed system controls have been verified by simulation studies and validated for Control hardware in a loop system consisting of one 500 kW Grid Forming converter and a 500 kW Grid Following Converter operating in parallel.

Indian Institute of Technology Roorkee (IN), Bharat Heavy Electricals (India) (IN)
Openalex Percentile: Top 43%
Islanding Detection in Power Systems
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

An Improved PLL-Based Control Technique for Seamless Transition Between Grid-Connected and Islanding Modes — Shoubhik Mukherjee, Anshu Priya, et al. · (2024) | TGRS Research Map | TGRS