Research on Analytical Calculation Method for DC Bias Characteristic of High Voltage Group Transformer

The calculation methods and characteristics analysis of transformer DC bias (TDB) are fundamental to researching the DC bias problems. Presently, the numerical calculation method is mainly adopted to solve the electromagnetic coupling equation of the transformer, which is unable to obtain the current expression and make precise TDB characteristics analysis. In this paper, the knee point of the magnetization curve is taken as the demarcation point of the calculation cycle. The electromagnetic coupling equation of the group transformer is solved analytically segment by segment, and time-domain expressions of winding current and excitation current in the unsaturated area and saturated area are obtained. The influence of TDB on the winding current and excitation current characteristic components is analyzed. On this basis, A calculation method for the DC bias current that causes critical saturation of the transformer is proposed. Furthermore, achieving the prediction of whether the core occurs saturated phenomenon under TDB. The validity and accuracy of the theoretical analysis are verified using the Matlab/Simulink simulation platform. The conclusions of the paper provide certain references for quantitatively analyzing the characteristics of TDB.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Power Delivery
Published
2025-03-26
DOI
https://doi.org/10.1109/tpwrd.2025.3554705
Citations
5
Primary Topic
Power Systems and Technologies
Type
article
Field-Weighted Citation Impact
3.65
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on Analytical Calculation Method for DC Bias Characteristic of High Voltage Group Transformer

Botong Li, Weijie Wen, Bin Li, Siyuan Liu et al.
5 citations
IEEE Transactions on Power Delivery
Power Systems and Technologies
3.65
article

Research on Analytical Calculation Method for DC Bias Characteristic of High Voltage Group Transformer

Botong Li, Weijie Wen, Bin Li, Siyuan Liu, Qing Li
article en
5 citations

Abstract

The calculation methods and characteristics analysis of transformer DC bias (TDB) are fundamental to researching the DC bias problems. Presently, the numerical calculation method is mainly adopted to solve the electromagnetic coupling equation of the transformer, which is unable to obtain the current expression and make precise TDB characteristics analysis. In this paper, the knee point of the magnetization curve is taken as the demarcation point of the calculation cycle. The electromagnetic coupling equation of the group transformer is solved analytically segment by segment, and time-domain expressions of winding current and excitation current in the unsaturated area and saturated area are obtained. The influence of TDB on the winding current and excitation current characteristic components is analyzed. On this basis, A calculation method for the DC bias current that causes critical saturation of the transformer is proposed. Furthermore, achieving the prediction of whether the core occurs saturated phenomenon under TDB. The validity and accuracy of the theoretical analysis are verified using the Matlab/Simulink simulation platform. The conclusions of the paper provide certain references for quantitatively analyzing the characteristics of TDB.

IEEE Transactions on Power DeliveryVol. 40(3)
Tianjin University (CN)
Affordable and clean energy
Openalex Percentile: Top 7%
Power Systems and Technologies
3.65
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.