Coordinated Control System Design for Inverters in Distributed Power Generation
Aiming at the coordinated control problem of grid-connected inverters in distributed generation systems, a control strategy based on distributed algorithms is designed. A 50kW experimental platform consisting of 12 inverters is built to test the system performance. The experimental results show that: the maximum frequency deviation during islanding switching is 0.13Hz, the recovery time is 185ms; the dynamic adjustment time of power is 138ms, the overshoot is 9.2%; the total harmonic distortion rate of the system is 1.85%, and the power factor is 0.995. The control strategy has good dynamic performance and anti-interference ability, meeting the actual engineering requirements.
Authors
- Haoyang Feng (ORCID: https://orcid.org/0000-0003-0561-1380)
Institutions
- North China University of Technology (CN)
Publication Details
- Published
- 2024-12-27
- DOI
- https://doi.org/10.1109/eiecc64539.2024.10929545
- Primary Topic
- Microgrid Control and Optimization
- Type
- article
- Field-Weighted Citation Impact
- 0.00