A Networked Method Applied to Sensitivity Analysis of a VSG controlled BESS System
The grid-forming battery energy storage system (BESS) plays important role in constructing new energy system. This paper presents a frequency domain modal-based stability analysis of virtual synchronous generator (VSG) controlled BESS. Both ac and dc side interactive dynamics of the grid-tied inverter system are considered, by establishing a hybrid ac/dc impedance network. Then, the frequency domain modal analysis (FMA) method for networked converter systems is applied to the BESS system, covering the eigen-sensitivity from the node level to parameter level. Using this method, key parameters that influence the BESS system’s weakly/negative damping modes most can be better analyzed and identified. The analysis results are validated via the time-domain simulations.