Research on Internal Fault Analysis and Main Protection Design of Zhaoqing Variable-Speed Pumped-Storage Unit
The construction commencement of the Zhaoqing Pumped Storage Power Station represents a significant milestone in China's independent research and development of AC excitation generator-motor technology. This station is set to accommodate one 300MW variable-speed unit alongside three traditional 300MW constant-speed units. To ensure the proper protection of the variable-speed unit, this paper establishes the multi-loop mathematical model for an AC excitation generator-motor, validated through experimental testing. Moreover, by drawing upon quantitative design insights for the main protection of constant-speed units and simulations of typical internal fault scenarios, this paper also determines the appropriate grouping of stator winding branches and devises a scientifically grounded configuration for the Zhaoqing variable-speed unit's main protection scheme. The quantitative and optimized protection design process for the main protection system can provide a reference for the forthcoming construction of domestic variable-speed pumped storage power stations.
Authors
- Shiming Cheng
- Gao Ma (ORCID: https://orcid.org/0000-0002-9333-9227)
- Yun Wang (ORCID: https://orcid.org/0000-0002-7711-1126)
- Kai Wang (ORCID: https://orcid.org/0000-0003-0443-6955)
- Xie Zhang
Institutions
- NARI Group (China) (CN)
- China Southern Power Grid (China) (CN)
Publication Details
- Published
- 2024-10-25
- DOI
- https://doi.org/10.1109/appeec61255.2024.10922657
- Primary Topic
- Power Systems and Renewable Energy
- Type
- article
- Field-Weighted Citation Impact
- 0.00