An Improved Frequency Feedforward Control for the Grid-Forming Converter
In the 100% renewable energy penetration power system, due to the absence of the conventional synchronous generator, the grid-forming converters(GFCs) are required to offer more inertia power. The GFCs can be seen as a typical second-order dynamic system, which is hardly to balance multiple control objectives. The inertia time constant usually contradicts with the dynamic response indices, such as the response speed and overshoot suppression ability under the step response of the positive power. To solve these problems, the frequency at the PCC (Point of Common Coupling) is estimated by the SOGI-FLL (Second Order General Integrator Frequency Locked Loop) and filtered for the feedforward control of the positive power control loop in this paper. With this strategy, both the dynamic response and the inertia power support can be improved. Finally, experiments are conducted on a 228 kW PV string inverter to validate the effectiveness of the proposed strategy.
Authors
- Hongwei Zhou (ORCID: https://orcid.org/0000-0001-5086-4622)
- P. Li (ORCID: https://orcid.org/0000-0002-4236-5142)
- Zheng Wang (ORCID: https://orcid.org/0000-0003-4255-0206)
- Rui Wang (ORCID: https://orcid.org/0000-0001-6088-2891)
- Xiaoshuai Qin
- Shaoyi Ren
Institutions
- Tebian Electric Apparatus (China) (CN)
Publication Details
- Published
- 2024-10-25
- DOI
- https://doi.org/10.1109/appeec61255.2024.10922347
- Primary Topic
- Power Systems and Renewable Energy
- Type
- article
- Field-Weighted Citation Impact
- 0.00