Nonlinearity of the magnetization characteristic of the magnetic core in calculation of current error and phase displacement values of inductive CTs

This paper explores the implications of employing a load exhibiting a power factor of 1 to test the transformation accuracy of an inductive current transformer with an apparent power below 5 VA. It offers an explanation of the change in current error and phase displacement correlates with the load power factor. The impact of the load power factor on the secondary winding on the accuracy of inductive CT is investigated in detail. The paper introduces a newly developed method that allows for the calculation of current error and phase displacement values for any power factor with consideration of the nonlinearity of the magnetization characteristic of the magnetic core. To ensure required accuracy of calculations of utmost significance is the potential RMS value modification of the magnetic core excitation voltage, which may further impact the transformation accuracy. Consequently, the operational conditions during the test are modified, and, owing to the nonlinearity of the magnetization characteristic of the magnetic core, the values of current error and phase displacement are also changed-not only due to a different load power factor connected to the secondary winding of the tested inductive current transformer. To maintain consistent operational conditions for a given secondary winding load power factor, the resistance connected to the secondary winding during the accuracy test with the power factor equal to 1 should be corrected. Moreover, the findings of this paper lead to the conclusion that evaluation of the transformation accuracy of inductive current transformer for both secondary winding load power factors is essential to ensure its reliable future operation in real conditions with the required accuracy class.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2025-03-23
DOI
https://doi.org/10.1038/s41598-025-94803-7
Citations
6
Primary Topic
Electrical and Bioimpedance Tomography
Type
article
Field-Weighted Citation Impact
4.38
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Nonlinearity of the magnetization characteristic of the magnetic core in calculation of current error and phase displacement values of inductive CTs

M. Kaczmarek
6 citations
Scientific Reports
Electrical and Bioimpedance Tomography
4.38
article

Nonlinearity of the magnetization characteristic of the magnetic core in calculation of current error and phase displacement values of inductive CTs

M. Kaczmarek
article en
6 citations

Abstract

This paper explores the implications of employing a load exhibiting a power factor of 1 to test the transformation accuracy of an inductive current transformer with an apparent power below 5 VA. It offers an explanation of the change in current error and phase displacement correlates with the load power factor. The impact of the load power factor on the secondary winding on the accuracy of inductive CT is investigated in detail. The paper introduces a newly developed method that allows for the calculation of current error and phase displacement values for any power factor with consideration of the nonlinearity of the magnetization characteristic of the magnetic core. To ensure required accuracy of calculations of utmost significance is the potential RMS value modification of the magnetic core excitation voltage, which may further impact the transformation accuracy. Consequently, the operational conditions during the test are modified, and, owing to the nonlinearity of the magnetization characteristic of the magnetic core, the values of current error and phase displacement are also changed-not only due to a different load power factor connected to the secondary winding of the tested inductive current transformer. To maintain consistent operational conditions for a given secondary winding load power factor, the resistance connected to the secondary winding during the accuracy test with the power factor equal to 1 should be corrected. Moreover, the findings of this paper lead to the conclusion that evaluation of the transformation accuracy of inductive current transformer for both secondary winding load power factors is essential to ensure its reliable future operation in real conditions with the required accuracy class.

Scientific ReportsVol. 15(1)
Lodz University of Technology (PL)
Openalex Percentile: Top 6%
Electrical and Bioimpedance Tomography
4.38
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.