Operational Characteristics of Earth-Leakage Circuit Breakers in the Presence of Low-Current Series Arcs

This study examines the operational characteristics of earth-leakage circuit breakers (ELCBs) in response to low-current series arcs. Five 20 A ELCBs were selected as experimental specimens, and HFIX wires were used to apply currents of 5 A, 10 A, 15 A, and 20 A below the rated current as well as 30 A, representing overcurrent, to investigate how ELCBs respond to series arc generation. The results showed that at 15 A and 20 A, which correspond to series arc conditions below the rated current, a rapid temperature increase occurred due to arc energy. Sawdust ignited within 135-150 s and 30-35 s, respectively, indicating a significant fire risk. However, the ELCBs did not activate since the load remained below the rated current. When an overcurrent of 30 A was applied, some ELCBs were triggered and tripped under normal conditions. However, in the presence of a series arc fault, the fire risk was particularly high, as sawdust ignited before the ELCBs activated, or they operated only after the fire had already started. These findings highlight the limitations of ELCBs in detecting series arcs, emphasizing the need for additional protective devices such as arc-fault circuit interrupters (AFCIs).

Authors

Institutions

Publication Details

Journal
International Journal of Fire Science and Engineering
Published
2024-12-31
DOI
https://doi.org/10.7731/kifse.7cf2f451
Citations
1
Primary Topic
Vacuum and Plasma Arcs
Type
article
Field-Weighted Citation Impact
0.34
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Operational Characteristics of Earth-Leakage Circuit Breakers in the Presence of Low-Current Series Arcs

SeongBeom Kim
1 citations
International Journal of Fire Science and Engineering
Vacuum and Plasma Arcs
0.34
article

Operational Characteristics of Earth-Leakage Circuit Breakers in the Presence of Low-Current Series Arcs

SeongBeom Kim
article en
1 citations

Abstract

This study examines the operational characteristics of earth-leakage circuit breakers (ELCBs) in response to low-current series arcs. Five 20 A ELCBs were selected as experimental specimens, and HFIX wires were used to apply currents of 5 A, 10 A, 15 A, and 20 A below the rated current as well as 30 A, representing overcurrent, to investigate how ELCBs respond to series arc generation. The results showed that at 15 A and 20 A, which correspond to series arc conditions below the rated current, a rapid temperature increase occurred due to arc energy. Sawdust ignited within 135-150 s and 30-35 s, respectively, indicating a significant fire risk. However, the ELCBs did not activate since the load remained below the rated current. When an overcurrent of 30 A was applied, some ELCBs were triggered and tripped under normal conditions. However, in the presence of a series arc fault, the fire risk was particularly high, as sawdust ignited before the ELCBs activated, or they operated only after the fire had already started. These findings highlight the limitations of ELCBs in detecting series arcs, emphasizing the need for additional protective devices such as arc-fault circuit interrupters (AFCIs).

International Journal of Fire Science and EngineeringVol. 38(4)
National Research Institute of Fire and Disaster (JP)
Openalex Percentile: Top 37%
Vacuum and Plasma Arcs
0.34
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.