Physical modeling of the reverse transformation mode in a rural 0.4/10 kV electric grid

RELEVANCE. Currently, there is a danger of supplying unauthorized voltage in rural electrical networks of 0.4 kV, which through reverse transformation at a transformer substation can be supplied to the 10 kV side. This can lead to fatal accidents among the staff of power grid organizations, or third parties. THE PURPOSE. Investigation of the reverse transformation mode in a rural 10/0.4 kV electric grid by means of physical modeling. METHODS. The study was conducted on a physical model of a 10/0.4 kV rural electric network using a single-phase lowpower transformer as a source of unauthorized voltage, which was connected to a low-voltage network at different distances from the model of a three-phase 10/0.4 kV transformer. In the experiments, electrical parameters were measured on the low and high voltage sides of the 10/0.4 kV transformer model. The obtained values, using similarity coefficients, were recalculated for a rural 10/0.4 kV electric grid powered by a 10/0.4 kV transformer with a capacity of 250 kVA. RESULTS. It was revealed that connecting a single-phase unauthorized voltage source to a 0.4 kV network, depending on its removal from a 10/0.4 kV transformer, leads to voltage values at the 0.4 kV output of the transformer from 11 V to 81 V (when approaching the beginning of the line departing from the transformer) in the phase to which the unauthorized voltage source is connected. On the 10 kilovolt side, the voltage varies from 234 V to 2579 V. The voltages of the other two phases on the 10 kV side range from 66 to 421 V, and on the 0.4 kV side – from 4.4 V to 22 V. CONCLUSION. The results obtained can be used as setpoints for triggering technical means of signaling and blocking reverse transformation, preventing reverse transformation in electric networks of 10/0.4 kV.

Authors

Institutions

Publication Details

Journal
Power engineering research equipment technology
Published
2025-03-17
DOI
https://doi.org/10.30724/1998-9903-2025-27-1-59-69
Primary Topic
Power Systems and Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Physical modeling of the reverse transformation mode in a rural 0.4/10 kV electric grid

A. A. Lansberg, Alexander Vinogradov, A. A. Panfilov
3 links
Power engineering research equipment technology
Power Systems and Technologies
article

Physical modeling of the reverse transformation mode in a rural 0.4/10 kV electric grid

A. A. Lansberg, Alexander Vinogradov, A. A. Panfilov
article en

Abstract

RELEVANCE. Currently, there is a danger of supplying unauthorized voltage in rural electrical networks of 0.4 kV, which through reverse transformation at a transformer substation can be supplied to the 10 kV side. This can lead to fatal accidents among the staff of power grid organizations, or third parties. THE PURPOSE. Investigation of the reverse transformation mode in a rural 10/0.4 kV electric grid by means of physical modeling. METHODS. The study was conducted on a physical model of a 10/0.4 kV rural electric network using a single-phase lowpower transformer as a source of unauthorized voltage, which was connected to a low-voltage network at different distances from the model of a three-phase 10/0.4 kV transformer. In the experiments, electrical parameters were measured on the low and high voltage sides of the 10/0.4 kV transformer model. The obtained values, using similarity coefficients, were recalculated for a rural 10/0.4 kV electric grid powered by a 10/0.4 kV transformer with a capacity of 250 kVA. RESULTS. It was revealed that connecting a single-phase unauthorized voltage source to a 0.4 kV network, depending on its removal from a 10/0.4 kV transformer, leads to voltage values at the 0.4 kV output of the transformer from 11 V to 81 V (when approaching the beginning of the line departing from the transformer) in the phase to which the unauthorized voltage source is connected. On the 10 kilovolt side, the voltage varies from 234 V to 2579 V. The voltages of the other two phases on the 10 kV side range from 66 to 421 V, and on the 0.4 kV side – from 4.4 V to 22 V. CONCLUSION. The results obtained can be used as setpoints for triggering technical means of signaling and blocking reverse transformation, preventing reverse transformation in electric networks of 10/0.4 kV.

Power engineering research equipment technologyVol. 27(1)
Orel State Agrarian University (RU), Federal Scientific Agroengineering Center VIM (RU)
Openalex Percentile: Top 96%
Power Systems and Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Physical modeling of the reverse transformation mode in a rural 0.4/10 kV electric grid — A. A. Lansberg, Alexander Vinogradov, et al. · Power engineering research equipment technology (2025) | TGRS Research Map | TGRS