Parametric study and thermal sensitivity analysis of a triple effect absorption refrigeration system
Absorption refrigeration systems represent an efficient means of cooling utilizing waste heat, with triple-effect absorption refrigeration systems outperforming their double and single-effect counterparts in terms of efficiency. This study conducts energy and exergy analyses on a triple-effect absorption refrigeration system, focusing on internal heat balance and thermal sensitivity to maximize efficiency. The analysis pinpointed the most sensitive thermal sensitivity areas within the system, highlighting the high-pressure condenser (HPC) outlet and medium-pressure condenser (MPC) outlet as critical points. Notably, increasing the temperatures of HPC and MPC leads to enhanced COP and ECOP, with a mere 5 K rise in HPC exit temperature resulting in a remarkable 57 % boost in system performance. Similarly, elevating the MPC operating temperature by 5 K yields a significant 34 % improvement in COP value.
Authors
- Kenan Saka (ORCID: https://orcid.org/0000-0002-2296-894X)
- Mehmet F. Orhan (ORCID: https://orcid.org/0000-0002-6751-9101)
Institutions
- Bursa Uludağ Üni̇versi̇tesi̇ (TR)
- American University of Sharjah (AE)
- Yenişehir Hospital (TR)
Publication Details
- Journal
- Case Studies in Thermal Engineering
- Published
- 2025-03-17
- DOI
- https://doi.org/10.1016/j.csite.2025.106030
- Citations
- 5
- Primary Topic
- Advanced Thermodynamic Systems and Engines
- Type
- article
- Field-Weighted Citation Impact
- 3.57