Study of Erosion Shield Failure in Powerplant Steam Generator

Abstract This report gives a comprehensive investigation on the failure of Erosion Shields in the steam generator of a coal-fired power plant. The primary purpose of the Erosion Shield is to safeguard the superheater tube from potential erosion caused by the forceful discharge of soot blower and to mitigate the occurrence of slagging. In certain instances, it has been observed that Erosion Shield clamps may fracture and descend to the lower region of the steam generator, hence causing disruption to the operation of the bottom ash management system. In order to safeguard the superheater tube, the Erosion Shield is affixed and secured by the use of clamps and welding. Based on the observed data, it can be concluded that instances of failure are observed in both the clamp and weld components. In order to conduct a more comprehensive analysis, metallographic specimens of the clamp are made and subjected to hardness testing. The hardness of the weld metal is greater in comparison to the hardness of both the heat-affected zone (HAZ) and the base metal. The disparity in hardness between the E308 filler metal and the AISI 304 base metal is quite substantial. The analysis of the macrostructure reveals that the weld bead on the clamps exhibits an excessive height. This phenomenon can be attributed to the reduced bending angle shown by the clamp at its terminal point. The microstructure analysis of the Erosion Shield sample involves the study of certain test locations located in the base metal, heat affected zone (HAZ), fusion line, and weld metal. Sufficient characterization of the Erosion Shield material as austenitic stainless-steel type can be achieved by analyzing the microstructure of both the base metal and the heat-affected zone (HAZ). The observed grain structure of both the base metal and heat-affected zone (HAZ) did not exhibit any discernible differences. This can be attributed to the prolonged exposure of the Erosion Shield in a high-temperature gas environment ranging from 1200 to 1400°C. Furthermore, there is a lack of evidence suggesting the presence of intergranular corrosion at the grain boundary of both the base metal and heat-affected zone (HAZ).

Authors

Institutions

Publication Details

Journal
Journal of Physics Conference Series
Published
2025-03-01
DOI
https://doi.org/10.1088/1742-6596/2972/1/012064
Primary Topic
Erosion and Abrasive Machining
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Study of Erosion Shield Failure in Powerplant Steam Generator

Agung Nugroho, Hery Sonawan, Mohammad Reza Hermawan
Journal of Physics Conference Series
Erosion and Abrasive Machining
article

Study of Erosion Shield Failure in Powerplant Steam Generator

Agung Nugroho, Hery Sonawan, Mohammad Reza Hermawan
article en

Abstract

Abstract This report gives a comprehensive investigation on the failure of Erosion Shields in the steam generator of a coal-fired power plant. The primary purpose of the Erosion Shield is to safeguard the superheater tube from potential erosion caused by the forceful discharge of soot blower and to mitigate the occurrence of slagging. In certain instances, it has been observed that Erosion Shield clamps may fracture and descend to the lower region of the steam generator, hence causing disruption to the operation of the bottom ash management system. In order to safeguard the superheater tube, the Erosion Shield is affixed and secured by the use of clamps and welding. Based on the observed data, it can be concluded that instances of failure are observed in both the clamp and weld components. In order to conduct a more comprehensive analysis, metallographic specimens of the clamp are made and subjected to hardness testing. The hardness of the weld metal is greater in comparison to the hardness of both the heat-affected zone (HAZ) and the base metal. The disparity in hardness between the E308 filler metal and the AISI 304 base metal is quite substantial. The analysis of the macrostructure reveals that the weld bead on the clamps exhibits an excessive height. This phenomenon can be attributed to the reduced bending angle shown by the clamp at its terminal point. The microstructure analysis of the Erosion Shield sample involves the study of certain test locations located in the base metal, heat affected zone (HAZ), fusion line, and weld metal. Sufficient characterization of the Erosion Shield material as austenitic stainless-steel type can be achieved by analyzing the microstructure of both the base metal and the heat-affected zone (HAZ). The observed grain structure of both the base metal and heat-affected zone (HAZ) did not exhibit any discernible differences. This can be attributed to the prolonged exposure of the Erosion Shield in a high-temperature gas environment ranging from 1200 to 1400°C. Furthermore, there is a lack of evidence suggesting the presence of intergranular corrosion at the grain boundary of both the base metal and heat-affected zone (HAZ).

Journal of Physics Conference SeriesVol. 2972(1)
Indonesian Pediatric Society (ID), Universitas Pasundan (ID)
Openalex Percentile: Top 97%
Erosion and Abrasive Machining
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.