The Role of Mechanical Ventilation in Indoor Air Quality in Schools: An Experimental Comprehensive Analysis

Indoor air quality (IAQ) plays a vital role in supporting both the physical and mental well-being of individuals in enclosed spaces, and the role of mechanical ventilation systems has gained increasing attention due to building design’s focus on energy efficiency and thus airtight constructions. This study investigated the pre–post effects of installing a heat recovery mechanical ventilation system (MVHR) on indoor air quality in a high school classroom in Ferrara, Italy. The analysis focused on experimental measurements of temperature (T), relative humidity (RH), and carbon dioxide (CO2) both inside and outside the same classroom, which had constant occupancy (17 students) for an entire school year, allowing a comparison between natural and mechanical ventilation. With a comprehensive approach, particulate matter (PM2.5), volatile organic compounds (VOCs), and radon levels (Rn) were monitored as well, after the installation of the MVHR. By comparing natural and mechanical ventilation, the study highlights the strengths and limitations of the ventilation system implemented, together with an evaluation of the system’s energy consumption, including a 2 kW post-heating battery. In terms of results, the MVHR demonstrated clear benefits in managing CO2 levels and improving sensory, olfactory, and psychophysical well-being, as well as the attention levels of students. In detail, under natural ventilation, peak concentrations exceeded 4500 ppm, while mechanical ventilation kept them below 1500 ppm. The average CO2 concentration during occupancy dropped from 2500 ppm to around 1000 ppm, achieving a 62% reduction. However, beneficial effects were not observed for other parameters, such as PM2.5, VOCs, or radon. The latter displayed annual average values around 21 Bq/m3 and peaks reaching 56 Bq/m3.

Authors

Institutions

Publication Details

Journal
Buildings
Published
2025-03-11
DOI
https://doi.org/10.3390/buildings15060869
Citations
11
Primary Topic
Indoor Air Quality and Microbial Exposure
Type
article
Field-Weighted Citation Impact
13.20
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

The Role of Mechanical Ventilation in Indoor Air Quality in Schools: An Experimental Comprehensive Analysis

Maddalena Coccagna, Antonella Volta, Vincenzo Ballerini, Eugenia Rossi di Schio et al.
11 citations
Buildings
Indoor Air Quality and Microbial Exposure
13.20
article

The Role of Mechanical Ventilation in Indoor Air Quality in Schools: An Experimental Comprehensive Analysis

Maddalena Coccagna, Antonella Volta, Vincenzo Ballerini, Eugenia Rossi di Schio, Matteo Bisi, Sante Mazzacane, Paolo Valdiserri, Lorenzo Droghetti
article en
11 citations

Abstract

Indoor air quality (IAQ) plays a vital role in supporting both the physical and mental well-being of individuals in enclosed spaces, and the role of mechanical ventilation systems has gained increasing attention due to building design’s focus on energy efficiency and thus airtight constructions. This study investigated the pre–post effects of installing a heat recovery mechanical ventilation system (MVHR) on indoor air quality in a high school classroom in Ferrara, Italy. The analysis focused on experimental measurements of temperature (T), relative humidity (RH), and carbon dioxide (CO2) both inside and outside the same classroom, which had constant occupancy (17 students) for an entire school year, allowing a comparison between natural and mechanical ventilation. With a comprehensive approach, particulate matter (PM2.5), volatile organic compounds (VOCs), and radon levels (Rn) were monitored as well, after the installation of the MVHR. By comparing natural and mechanical ventilation, the study highlights the strengths and limitations of the ventilation system implemented, together with an evaluation of the system’s energy consumption, including a 2 kW post-heating battery. In terms of results, the MVHR demonstrated clear benefits in managing CO2 levels and improving sensory, olfactory, and psychophysical well-being, as well as the attention levels of students. In detail, under natural ventilation, peak concentrations exceeded 4500 ppm, while mechanical ventilation kept them below 1500 ppm. The average CO2 concentration during occupancy dropped from 2500 ppm to around 1000 ppm, achieving a 62% reduction. However, beneficial effects were not observed for other parameters, such as PM2.5, VOCs, or radon. The latter displayed annual average values around 21 Bq/m3 and peaks reaching 56 Bq/m3.

BuildingsVol. 15(6)
University of Ferrara (IT), University of Bologna (IT)
Openalex Percentile: Top 1%
Indoor Air Quality and Microbial Exposure
13.20
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.