Experimental study on operation limit of ground heat exchanger based on ground source heat pump unit

The heat transfer performance of a ground heat exchanger (GHE) directly influences the operational performance of a ground source heat pump (GSHP) system. The fluid temperature within the GHE is constrained by the protective temperature limits of the GSHP unit. Specifically, the inlet water temperature has an upper limit in summer and a lower limit in winter. These temperature limits further affect the heat exchange efficiency between the GHE and the surrounding soil. In this study, an experimental station featuring a single U-shaped GSHP system was constructed, and a three-dimensional model of the system was developed. Experiments were conducted by operating one or two GHEs to investigate the heat transfer per unit well depth and the matching relationship between cooling capacity and indoor load when the inlet water temperature of the heat pump unit approaches its summer and winter limits. In summer, when operating a single GHE, the heat transfer per unit well depth reached 134.4 W/m at an inlet temperature of 45 °C. When the cooling supply just matched the cooling load demand, the heat transfer per unit well depth was 131.5 W/m. However, prolonged operation led to a scenario where the cooling supply could no longer meet the load demand. In winter, operating a single GHE resulted in a heat transfer per unit well depth of 43.95 W/m at an inlet temperature of 5 °C. These results indicate that when the number of heat exchangers is insufficient, the inlet water temperature of the heat pump unit may reach or exceed the limit value, leading to decreased unit efficiency. Additionally, inadequate heat exchange between the GHE and the soil results in insufficient cooling or heating capacity, failing to meet the indoor load requirements.

Authors

Publication Details

Journal
PLoS ONE
Published
2025-03-11
DOI
https://doi.org/10.1371/journal.pone.0319430
Citations
3
Primary Topic
Geothermal Energy Systems and Applications
Type
article
Field-Weighted Citation Impact
1.09
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental study on operation limit of ground heat exchanger based on ground source heat pump unit

Rui Zhang
3 citations
PLoS ONE
Geothermal Energy Systems and Applications
1.09
article

Experimental study on operation limit of ground heat exchanger based on ground source heat pump unit

Rui Zhang
article en
3 citations

Abstract

The heat transfer performance of a ground heat exchanger (GHE) directly influences the operational performance of a ground source heat pump (GSHP) system. The fluid temperature within the GHE is constrained by the protective temperature limits of the GSHP unit. Specifically, the inlet water temperature has an upper limit in summer and a lower limit in winter. These temperature limits further affect the heat exchange efficiency between the GHE and the surrounding soil. In this study, an experimental station featuring a single U-shaped GSHP system was constructed, and a three-dimensional model of the system was developed. Experiments were conducted by operating one or two GHEs to investigate the heat transfer per unit well depth and the matching relationship between cooling capacity and indoor load when the inlet water temperature of the heat pump unit approaches its summer and winter limits. In summer, when operating a single GHE, the heat transfer per unit well depth reached 134.4 W/m at an inlet temperature of 45 °C. When the cooling supply just matched the cooling load demand, the heat transfer per unit well depth was 131.5 W/m. However, prolonged operation led to a scenario where the cooling supply could no longer meet the load demand. In winter, operating a single GHE resulted in a heat transfer per unit well depth of 43.95 W/m at an inlet temperature of 5 °C. These results indicate that when the number of heat exchangers is insufficient, the inlet water temperature of the heat pump unit may reach or exceed the limit value, leading to decreased unit efficiency. Additionally, inadequate heat exchange between the GHE and the soil results in insufficient cooling or heating capacity, failing to meet the indoor load requirements.

PLoS ONEVol. 20(3)
Openalex Percentile: Top 25%
Geothermal Energy Systems and Applications
1.09
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.