Development and Performance Evaluation of Low-Noise Integrated and Separated Type Portable HEPA Filter Units for Temporary Negative Pressure Isolation Rooms
This study aimed to address noise issues and concerns regarding contaminant re-entry in temporary negative pressure isolation rooms equipped with portable negative pressure units. To achieve this, we developed low-noise integrated portable HEPA filter unit and separated unit, in which fan and filter components were divided. We then evaluated their performance in both a healthcare facility and a simulated chamber, comparing with the existing integrated unit currently used in healthcare facilities. Results showed that the low-noise integrated unit significantly reduced noise levels compared to the existing integrated unit. The separated unit exhibited similar noise levels to the low-noise integrated unit at lower airflow rates but exhibited lower noise levels compared to the integrated unit as airflow increased. The separated unit also effectively prevented contaminant re-entry, with lower tracer gas concentrations observed in the patient room and hallway compared to the integrated unit during the chamber experiment.
Authors
- Tae‐Young Park (ORCID: https://orcid.org/0000-0002-0626-7289)
- Jin-Ho Roh (ORCID: https://orcid.org/0000-0002-4496-1490)
- Won‐Seok Lee (ORCID: https://orcid.org/0009-0003-6180-4133)
- Sejin Lee (ORCID: https://orcid.org/0000-0003-2834-1109)
- Myoung Souk Yeo
- Daehyeok Park
Publication Details
- Journal
- Korean Journal of Air-Conditioning and Refrigeration Engineering
- Published
- 2025-03-11
- DOI
- https://doi.org/10.6110/kjacr.2025.37.3.151
- Primary Topic
- Context-Aware Activity Recognition Systems
- Type
- article
- Field-Weighted Citation Impact
- 0.00