Impacts of Earthing Variations on Overvoltage in Meshed Multi-terminal DC Grid
This paper investigates the impact of different earthing methods on overvoltage within modular multilevel Voltage Source Converter (MMC VSC) based Direct Current (DC) transmission and distribution grids, particularly in meshed multi-terminal (MTDC) configurations. A bipolar MTDC grid is modelled and simulated in PSCAD/EMTDC to investigate the influence of earthing on midpoint overvoltages. The transient response of the grid under DC fault scenarios is analysed through various case-studies, including solid earthing placement, variations in earthing impedance, and the application of surge arresters. The findings show the critical role of earthing in mitigating overvoltage, with low-resistive earthing options proving to be the most effective trade-off.