DC-link Thyristor-based Protection for HB-MMC HVDC Systems under Valve-side Single-phase-to-ground Faults

Valve-side, single-phase-to-ground (SPG) faults in bipolar high-voltage direct current (HVDC) systems based on half-bridge modular multilevel converters (HB-MMCs) result in i) significant upper arm overvoltage, and ii) non-zero-crossing currents in the grid-side ac circuit breaker (ACCB). In this paper, a dc-link thyristor-based protection scheme is proposed to address both issues. The dc-link thyristor branches are installed in the dc terminal of each station. A dc short-circuit loop is formed following triggering the thyristor branch, redirecting currents from the upper arms to the branch, thus preventing continuous capacitor charging in the upper arms. Moreover, the creation of the dc short-circuit loop induces symmetrical components in the grid-side currents, which ensure current zero-crossings in the grid-side ACCB. The peak current flowing into the dc-link thyristor branch is also calculated to facilitate the design of the thyristor branch. The effectiveness of the proposed protection scheme is validated in an HB-MMC HVDC system simulated in PSCAD/EMTDC.

Authors

Institutions

Publication Details

Published
2024-11-03
DOI
https://doi.org/10.1109/iecon55916.2024.10905958
Citations
1
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.21

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

DC-link Thyristor-based Protection for HB-MMC HVDC Systems under Valve-side Single-phase-to-ground Faults

Pingyang Sun, Georgios Konstantinou, Gen Li
1 citations
HVDC Systems and Fault Protection
0.21
article

DC-link Thyristor-based Protection for HB-MMC HVDC Systems under Valve-side Single-phase-to-ground Faults

Pingyang Sun, Georgios Konstantinou, Gen Li
article en
1 citations

Abstract

Valve-side, single-phase-to-ground (SPG) faults in bipolar high-voltage direct current (HVDC) systems based on half-bridge modular multilevel converters (HB-MMCs) result in i) significant upper arm overvoltage, and ii) non-zero-crossing currents in the grid-side ac circuit breaker (ACCB). In this paper, a dc-link thyristor-based protection scheme is proposed to address both issues. The dc-link thyristor branches are installed in the dc terminal of each station. A dc short-circuit loop is formed following triggering the thyristor branch, redirecting currents from the upper arms to the branch, thus preventing continuous capacitor charging in the upper arms. Moreover, the creation of the dc short-circuit loop induces symmetrical components in the grid-side currents, which ensure current zero-crossings in the grid-side ACCB. The peak current flowing into the dc-link thyristor branch is also calculated to facilitate the design of the thyristor branch. The effectiveness of the proposed protection scheme is validated in an HB-MMC HVDC system simulated in PSCAD/EMTDC.

UNSW Sydney (AU)
Australian Research Council
Affordable and clean energy
Openalex Percentile: Top 43%
HVDC Systems and Fault Protection
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

DC-link Thyristor-based Protection for HB-MMC HVDC Systems under Valve-side Single-phase-to-ground Faults — Pingyang Sun, Georgios Konstantinou, et al. · (2024) | TGRS Research Map | TGRS