Decoupled, Decentralized, LQR-Based Controls for E3 HEMP/GMD Mitigation on the Power Grid

High altitude electromagnetic pulses (HEMPs) and solar-geomagnetic disturbances (GMDs) both have the potential to impact the reliable operation of the electric power grid. GMDs, and the low-frequency portion of HEMP insults, introduce currents into the grid that can result in the magnetic cores of large power transformers becoming saturated. This paper presents a novel approach to HEMP/GMD mitigation, wherein actively controlled voltage sources are utilized to nullify a low frequency EMP insult. This method is evaluated on several power system case studies, including a single transformer system, a 20-bus system, and a 150-bus system. Results show that the active mitigation is able to successfully prevent transformer saturation in all cases.

Authors

Institutions

Publication Details

Published
2024-11-03
DOI
https://doi.org/10.1109/iecon55916.2024.10905555
Citations
5
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
1.04
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Decoupled, Decentralized, LQR-Based Controls for E3 HEMP/GMD Mitigation on the Power Grid

Wayne W. Weaver, Timothy Donnelly, Rush D. Robinett, Connor A. Lehman et al.
5 citations
HVDC Systems and Fault Protection
1.04
article

Decoupled, Decentralized, LQR-Based Controls for E3 HEMP/GMD Mitigation on the Power Grid

Wayne W. Weaver, Timothy Donnelly, Rush D. Robinett, Connor A. Lehman, David Gordon Wilson
article en
5 citations

Abstract

High altitude electromagnetic pulses (HEMPs) and solar-geomagnetic disturbances (GMDs) both have the potential to impact the reliable operation of the electric power grid. GMDs, and the low-frequency portion of HEMP insults, introduce currents into the grid that can result in the magnetic cores of large power transformers becoming saturated. This paper presents a novel approach to HEMP/GMD mitigation, wherein actively controlled voltage sources are utilized to nullify a low frequency EMP insult. This method is evaluated on several power system case studies, including a single transformer system, a 20-bus system, and a 150-bus system. Results show that the active mitigation is able to successfully prevent transformer saturation in all cases.

Michigan Technological University (US), Sandia National Laboratories (US)
Climate action
Openalex Percentile: Top 22%
HVDC Systems and Fault Protection
1.04
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.