The stability and elimination of mammalian enveloped and non-enveloped respiratory and enteric viruses in indoor air: Testing using a room-sized aerobiology chamber

We assessed the viability of aerosolized human betacoronavirus OC43 (HCoV-OC43; ATCC VR-1558), human rhinovirus-14 (RV-14; ATCC VR-284) and feline calicivirus (FCV; ATCC VR-782) as representative enveloped and non-enveloped respiratory and enteric viruses of mammals in indoor air under ambient conditions (relative humidity 50 ± 10 % and air temperature 22 ± 2°C) using a room-sized (25 m<sup>3</sup>; 900 ft<sup>3</sup>) aerobiology chamber. All virus suspensions contained a soil load to simulate the presence of body fluids and they were separately aerosolized into the chamber using a six-jet Collison nebulizer. A muffin fan was used to uniformly mix the air inside the chamber and to keep the aerosols airborne. A slit sampler with Petri plates containing 3 % (wt./vol) gelatin was used to collect the air samples. The gelatin was liquefied in an incubator and assayed for infectious virus as plaque-forming units (PFU). The rates of biological decay of HCoV-OC43, RV-14 and FCV were 0.0052 ± 0.00026, 0.0034 ± 0.0027 and 0.0081 ± 0.0031 (as log<sub>10</sub> PFU/m<sup>3</sup>/min), respectively. We also assessed a HEPA filter-based stand-alone air purifier against the experimentally aerosolized viruses and the device could demonstrate > 3-log<sub>10</sub> reductions in the viability of the three viruses in 46, 62 and 41 minutes, respectively. Therefore, we can now investigate the stability of mammalian viruses in indoor air as well as air decontamination technologies against them under field-relevant conditions.

Authors

Institutions

Publication Details

Journal
Journal of Virological Methods
Published
2025-03-08
DOI
https://doi.org/10.1016/j.jviromet.2025.115144
Citations
1
Primary Topic
Infection Control and Ventilation
Type
article
Field-Weighted Citation Impact
1.52
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

The stability and elimination of mammalian enveloped and non-enveloped respiratory and enteric viruses in indoor air: Testing using a room-sized aerobiology chamber

Syed A. Sattar, Julie McKinney, Bahram Zargar, M. Khalid Ijaz
1 citations
Journal of Virological Methods
Infection Control and Ventilation
1.52
article

The stability and elimination of mammalian enveloped and non-enveloped respiratory and enteric viruses in indoor air: Testing using a room-sized aerobiology chamber

Syed A. Sattar, Julie McKinney, Bahram Zargar, M. Khalid Ijaz
article en
1 citations

Abstract

We assessed the viability of aerosolized human betacoronavirus OC43 (HCoV-OC43; ATCC VR-1558), human rhinovirus-14 (RV-14; ATCC VR-284) and feline calicivirus (FCV; ATCC VR-782) as representative enveloped and non-enveloped respiratory and enteric viruses of mammals in indoor air under ambient conditions (relative humidity 50 ± 10 % and air temperature 22 ± 2°C) using a room-sized (25 m<sup>3</sup>; 900 ft<sup>3</sup>) aerobiology chamber. All virus suspensions contained a soil load to simulate the presence of body fluids and they were separately aerosolized into the chamber using a six-jet Collison nebulizer. A muffin fan was used to uniformly mix the air inside the chamber and to keep the aerosols airborne. A slit sampler with Petri plates containing 3 % (wt./vol) gelatin was used to collect the air samples. The gelatin was liquefied in an incubator and assayed for infectious virus as plaque-forming units (PFU). The rates of biological decay of HCoV-OC43, RV-14 and FCV were 0.0052 ± 0.00026, 0.0034 ± 0.0027 and 0.0081 ± 0.0031 (as log<sub>10</sub> PFU/m<sup>3</sup>/min), respectively. We also assessed a HEPA filter-based stand-alone air purifier against the experimentally aerosolized viruses and the device could demonstrate > 3-log<sub>10</sub> reductions in the viability of the three viruses in 46, 62 and 41 minutes, respectively. Therefore, we can now investigate the stability of mammalian viruses in indoor air as well as air decontamination technologies against them under field-relevant conditions.

Journal of Virological MethodsVol. 335
Credit Valley Hospital (CA), CARE Canada (CA), Reckitt Benckiser (United States) (US)
Openalex Percentile: Top 21%
Infection Control and Ventilation
1.52
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

The stability and elimination of mammalian enveloped and non-enveloped respiratory and enteric viruses in indoor air: Testing using a room-sized aerobiology chamber — Syed A. Sattar, Julie McKinney, et al. · Journal of Virological Methods (2025) | TGRS Research Map | TGRS