Experimental performance examination of a coherence technique-based numerical differential current relay for AC machine stator windings protection

A computational technique based on a coherence method for fault detection and classification for electrical machine stator windings is presented in this article. The coherence algorithm can identify clearly and concisely inter-turn and shunt faults situated on the 3-phase stator windings of the AC machine. Besides, it can categorize the different types of internal shunt faults. The cross-coherence algorithm performs the functional role of digital differential current to find and classify the internal faults; while, the auto-coherence algorithm acts as an overcurrent detector to define the occurrence of external, internal, or inter-turn faults. A new setup of three-phase induction machine stator windings, where each winding is re-winded to produce 20 taps per phase, is used to examine the approach. The new design is intended to build current transformers at the neutral and supply sides of the three windings, and to simplify conducting comprehensive examinations to verify the efficacy and efficiency of the advanced algorithm. The protection characteristics of the developed algorithm will be analyzed and estimated using the new setup. The test results indicate that the reliability and accuracy of the protection are above 98.7%. The coherence criterion is also useful for monitoring electrical faults, sensing inter-turn faults, distinguishing between external and internal shunt faults, classifying diverse internal shunt faults within the equipment protection zone, and estimating the tripping time when inter-turn faults occur. Furthermore, a new design of protection tripping-characteristic curves is established, and the time response of the computational technique is fast.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2025-03-05
DOI
https://doi.org/10.1038/s41598-025-89092-z
Citations
3
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
3.64
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental performance examination of a coherence technique-based numerical differential current relay for AC machine stator windings protection

R. A. Mahmoud
3 citations
Scientific Reports
Power Systems Fault Detection
3.64
article

Experimental performance examination of a coherence technique-based numerical differential current relay for AC machine stator windings protection

R. A. Mahmoud
article en
3 citations

Abstract

A computational technique based on a coherence method for fault detection and classification for electrical machine stator windings is presented in this article. The coherence algorithm can identify clearly and concisely inter-turn and shunt faults situated on the 3-phase stator windings of the AC machine. Besides, it can categorize the different types of internal shunt faults. The cross-coherence algorithm performs the functional role of digital differential current to find and classify the internal faults; while, the auto-coherence algorithm acts as an overcurrent detector to define the occurrence of external, internal, or inter-turn faults. A new setup of three-phase induction machine stator windings, where each winding is re-winded to produce 20 taps per phase, is used to examine the approach. The new design is intended to build current transformers at the neutral and supply sides of the three windings, and to simplify conducting comprehensive examinations to verify the efficacy and efficiency of the advanced algorithm. The protection characteristics of the developed algorithm will be analyzed and estimated using the new setup. The test results indicate that the reliability and accuracy of the protection are above 98.7%. The coherence criterion is also useful for monitoring electrical faults, sensing inter-turn faults, distinguishing between external and internal shunt faults, classifying diverse internal shunt faults within the equipment protection zone, and estimating the tripping time when inter-turn faults occur. Furthermore, a new design of protection tripping-characteristic curves is established, and the time response of the computational technique is fast.

Scientific ReportsVol. 15(1)
Misr University for Science and Technology (EG)
Affordable and clean energy
Openalex Percentile: Top 8%
Power Systems Fault Detection
3.64
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.