Optimized Economizer Control with Maximum Limit Set-Point to Enhance Cooling Energy Performance in Korean Climate

An air handling unit utilizes economizer control to reduce cooling energy consumption by intaking outdoor air (OA) at lower temperatures. This control modulates OA intake rates based on the OA temperature, adjusting to maximum and partial rates when the OA temperature is below the maximum limit set-point (MLSP), and to minimum rates when it exceeds the MLSP. The MLSP acts as a baseline for determining OA intake rates. However, current MLSPs do not account for the specific OA conditions in South Korea, leading to the intake of unnecessarily warm OA or underutilization of available cooler OA, both of which negatively impact cooling energy performance. Therefore, this study aims to identify the optimal MLSP for OA conditions in South Korea. Through evaluation of cooling energy performance and the indoor thermal environment at various MLSP, it was determined that an MLSP of 22 °C facilitates the lowest cooling energy consumption without adversely affecting the indoor thermal environment. Implementing this MLSP resulted in 5.9% energy savings compared to Case #1 (baseline). The findings indicate that setting an MLSP according to local OA conditions is crucial for maximizing energy savings through economizer control.

Authors

Institutions

Publication Details

Journal
Applied Sciences
Published
2025-03-05
DOI
https://doi.org/10.3390/app15052825
Citations
1
Primary Topic
Energy and Environmental Systems
Type
article
Field-Weighted Citation Impact
2.18

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Optimized Economizer Control with Maximum Limit Set-Point to Enhance Cooling Energy Performance in Korean Climate

Chanuk Lee, Sung Lok, Minho Kim, Ahmin Jang
1 citations
Applied Sciences
Energy and Environmental Systems
2.18
article

Optimized Economizer Control with Maximum Limit Set-Point to Enhance Cooling Energy Performance in Korean Climate

Chanuk Lee, Sung Lok, Minho Kim, Ahmin Jang
article en
1 citations

Abstract

An air handling unit utilizes economizer control to reduce cooling energy consumption by intaking outdoor air (OA) at lower temperatures. This control modulates OA intake rates based on the OA temperature, adjusting to maximum and partial rates when the OA temperature is below the maximum limit set-point (MLSP), and to minimum rates when it exceeds the MLSP. The MLSP acts as a baseline for determining OA intake rates. However, current MLSPs do not account for the specific OA conditions in South Korea, leading to the intake of unnecessarily warm OA or underutilization of available cooler OA, both of which negatively impact cooling energy performance. Therefore, this study aims to identify the optimal MLSP for OA conditions in South Korea. Through evaluation of cooling energy performance and the indoor thermal environment at various MLSP, it was determined that an MLSP of 22 °C facilitates the lowest cooling energy consumption without adversely affecting the indoor thermal environment. Implementing this MLSP resulted in 5.9% energy savings compared to Case #1 (baseline). The findings indicate that setting an MLSP according to local OA conditions is crucial for maximizing energy savings through economizer control.

Applied SciencesVol. 15(5)
Hanbat National University (KR)
National Research Foundation of Korea
Openalex Percentile: Top 15%
Energy and Environmental Systems
2.18
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.