In view of the problem that a high proportion of Distributed Generation (DG) connected to the power distribution network makes traditional stage-based current protection inapplicable, a new principle of pilot protection based on the difference between the faulty negative-sequence current ratio and the current THDi is proposed. First, the characteristics of the fault current on the active distribution network side and the DG side are analysed, taking into account the characteristics of negative-sequence current suppression and the distortion of fault current of distributed photovoltaic. Second, protection criteria based on the faulty negative-sequence current ratio are proposed for asymmetric faults, and protection criteria based on the difference between the THDi of the fault current are proposed for symmetry faults. Finally, the effectiveness and reliability of this protection scheme is verified by building a pscad model. This protection scheme only requires transient information about the fault current at both ends and does not require voltage information, which can effectively reduce the difficulty of on-site construction.

Authors

Institutions

Publication Details

Published
2024-12-06
DOI
https://doi.org/10.1109/icips64173.2024.10900297
Primary Topic
Risk and Safety Analysis
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A New Principle of Pilot Protection based on the Ratio of Fault Negative-Sequence Current and the Difference of THDi

Yuanbo Ye, Jiwen Wang, Wenzheng Li, Ping Xia
Risk and Safety Analysis
article

A New Principle of Pilot Protection based on the Ratio of Fault Negative-Sequence Current and the Difference of THDi

Yuanbo Ye, Jiwen Wang, Wenzheng Li, Ping Xia
article en

Abstract

In view of the problem that a high proportion of Distributed Generation (DG) connected to the power distribution network makes traditional stage-based current protection inapplicable, a new principle of pilot protection based on the difference between the faulty negative-sequence current ratio and the current THDi is proposed. First, the characteristics of the fault current on the active distribution network side and the DG side are analysed, taking into account the characteristics of negative-sequence current suppression and the distortion of fault current of distributed photovoltaic. Second, protection criteria based on the faulty negative-sequence current ratio are proposed for asymmetric faults, and protection criteria based on the difference between the THDi of the fault current are proposed for symmetry faults. Finally, the effectiveness and reliability of this protection scheme is verified by building a pscad model. This protection scheme only requires transient information about the fault current at both ends and does not require voltage information, which can effectively reduce the difficulty of on-site construction.

China XD Group (China) (CN)
State Grid Corporation of China
Climate action
Openalex Percentile: Top 73%
Risk and Safety Analysis
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

A New Principle of Pilot Protection based on the Ratio of Fault Negative-Sequence Current and the Difference of THDi — Yuanbo Ye, Jiwen Wang, et al. · (2024) | TGRS Research Map | TGRS