Temperature distribution in a panel-radiant heating system
In this study, a computer model was developed in Comsol Multiphysics to determine and evaluate the temperature distribution in a panel-radiant heating system with a heated floor. A panel-radiant heating system consisting of a concrete layer with dimensions of 4 × 3.3 × 0.1 m³ was selected, and copper pipes with an inner diameter of 2 cm and total lengths of 64.84 m and 64.24 m were installed within this volume. Water was used as the heat carrier. The calculations revealed that in the second configuration, the temperature distribution on the surface of the panel-radiant heated floor system is relatively uniform and does not exceed the required value.
Authors
- K. A. Samiev (ORCID: https://orcid.org/0000-0002-3338-6208)
- J.J. Kamolov
Publication Details
- Journal
- International Journal of Science and Research Archive
- Published
- 2025-02-28
- DOI
- https://doi.org/10.30574/ijsra.2025.14.2.0560
- Primary Topic
- Radiative Heat Transfer Studies
- Type
- article
- Field-Weighted Citation Impact
- 0.00