A Self-Configurable BUS Network Topology Based on LoRa Nodes for the Transmission of Data and Alarm Messages in Power Line-Monitoring Systems
Power transmission lines transfer energy between power plants and substations by means of a linear chain of towers. These towers are often situated over extensive distances, sometimes in regions that are difficult to access. Wireless sensor networks present a viable solution for monitoring these long chains of towers due to their wide coverage, ease of installation and cost-effectiveness. The proposed LoRaBUS approach implements and analyses the benefits of a linear topology using a mixture of LoRa and LoRaWAN protocols. This approach is designed to enable automatic detection of nearby nodes, optimise energy consumption and provide a prioritised transmission mode in emergency situations. On remote, hard-to-reach towers, a prototype fire protection system was implemented and tested. The results demonstrate that LoRaBUS creates a self-configurable linear topology which proves advantageous for installation processes, node maintenance and troubleshooting node failures. The discovery process collects data from a neighbourhood to construct the network and to save energy. The network's autonomous configuration can be completed within approximately 2 min. In addition, energy consumption is effectively reduced 25% by dynamically adjusting the transmission power based on the detected channel quality and the distance to the nearest neighbour nodes.
Authors
- E. Isern (ORCID: https://orcid.org/0000-0001-9332-794X)
- B. Alorda (ORCID: https://orcid.org/0000-0002-5617-6254)
- M. Alabau Pons
Institutions
- Health Research Institute of the Balearic Islands (ES)
- Universitat de les Illes Balears (ES)
Publication Details
- Journal
- Sensors
- Published
- 2025-02-28
- DOI
- https://doi.org/10.3390/s25051484
- Citations
- 5
- Primary Topic
- IoT Networks and Protocols
- Type
- article
- Field-Weighted Citation Impact
- 3.65