A state estimator using synchronized phasor measurements for power systems containing VSC-HVDC links with converter losses

This article focuses on enhancing the formulation and implementation of state estimator (SE) using phasor measurements units (PMU) for transmission systems including voltage source converter (VSC) based high voltage direct current (HVDC) links. An equality constrained SE considering synchronized phasor measurements for hybrid power systems is proposed, where AC/DC power losses in the VSC station are taken into consideration. The associated measurement model encompasses both AC and DC measurements. For the AC network, PMU devices supply with synchronized voltage and current phasor measurements the SE. DC measurements are acquired from the DC side of the VSC stations and are assumed to be sampled at the same rate as the synchronized phasor measurements. Zero injections and AC/DC coupling equations are modeled as equality constraints. The effectiveness and estimation accuracy of the proposed algorithm are demonstrated on complex AC/HVDC test systems.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-02-01
DOI
https://doi.org/10.1049/icp.2024.4662
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A state estimator using synchronized phasor measurements for power systems containing VSC-HVDC links with converter losses

Georgios I. Karvelis, George N. Korres
IET conference proceedings.
HVDC Systems and Fault Protection
article

A state estimator using synchronized phasor measurements for power systems containing VSC-HVDC links with converter losses

Georgios I. Karvelis, George N. Korres
article en

Abstract

This article focuses on enhancing the formulation and implementation of state estimator (SE) using phasor measurements units (PMU) for transmission systems including voltage source converter (VSC) based high voltage direct current (HVDC) links. An equality constrained SE considering synchronized phasor measurements for hybrid power systems is proposed, where AC/DC power losses in the VSC station are taken into consideration. The associated measurement model encompasses both AC and DC measurements. For the AC network, PMU devices supply with synchronized voltage and current phasor measurements the SE. DC measurements are acquired from the DC side of the VSC stations and are assumed to be sampled at the same rate as the synchronized phasor measurements. Zero injections and AC/DC coupling equations are modeled as equality constraints. The effectiveness and estimation accuracy of the proposed algorithm are demonstrated on complex AC/HVDC test systems.

IET conference proceedings.Vol. 2024(29)
National Technical University of Athens (GR)
Affordable and clean energy
Openalex Percentile: Top 97%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.