Experimental Study of a Novel Prototype of Dual-Cycle Two-Phase Cooling System for a Data Cabinet

As Information Technology continues to rapidly evolve, the scale and energy consumption of data centers have seen a significant surge. Traditional air-cooling systems in data centers are notably energy intensive. This study proposes an innovative dual-cycle two-phase cooling system (DTCS) for retrofitting existing server cabinets. The system integrates the two synergistic subsystems of a pump-driven chip-level two-phase cooling system (PCTCS) and a pump-driven backplane-level two-phase cooling system (PBTCS). The PCTCS provides year-round natural cooling of high-power chips, and experimental results indicate that even under extreme outdoor conditions of up to 42 °C, the PCTCS can maintain the chip temperature at 76 °C. At the same time, the PBTCS effectively cools all components in the cabinet except the high-power chips. By efficiently controlling the chip temperature through the PCTCS, the novel DTCS ensures stable operation at data room temperatures up to 33 °C, thereby significantly reducing the energy consumption of the cooling system. The average annual pPUE of the cooling system is 1.078 at the test site in Xiangyang, Hubei province in China. The DTCS could perform well across various Chinese cities even under severe hot and moist conditions, with the average annual pPUE consistently below 1.1.

Authors

Institutions

Publication Details

Journal
Applied Sciences
Published
2025-02-23
DOI
https://doi.org/10.3390/app15052386
Citations
1
Primary Topic
Heat Transfer and Boiling Studies
Type
article
Field-Weighted Citation Impact
0.71
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental Study of a Novel Prototype of Dual-Cycle Two-Phase Cooling System for a Data Cabinet

Leixin Wang, Yifan Zhao, Kexian Ren, Tongzhi Yang et al.
1 citations
Applied Sciences
Heat Transfer and Boiling Studies
0.71
article

Experimental Study of a Novel Prototype of Dual-Cycle Two-Phase Cooling System for a Data Cabinet

Leixin Wang, Yifan Zhao, Kexian Ren, Tongzhi Yang, Weixing Yuan, Hao Cheng
article en
1 citations

Abstract

As Information Technology continues to rapidly evolve, the scale and energy consumption of data centers have seen a significant surge. Traditional air-cooling systems in data centers are notably energy intensive. This study proposes an innovative dual-cycle two-phase cooling system (DTCS) for retrofitting existing server cabinets. The system integrates the two synergistic subsystems of a pump-driven chip-level two-phase cooling system (PCTCS) and a pump-driven backplane-level two-phase cooling system (PBTCS). The PCTCS provides year-round natural cooling of high-power chips, and experimental results indicate that even under extreme outdoor conditions of up to 42 °C, the PCTCS can maintain the chip temperature at 76 °C. At the same time, the PBTCS effectively cools all components in the cabinet except the high-power chips. By efficiently controlling the chip temperature through the PCTCS, the novel DTCS ensures stable operation at data room temperatures up to 33 °C, thereby significantly reducing the energy consumption of the cooling system. The average annual pPUE of the cooling system is 1.078 at the test site in Xiangyang, Hubei province in China. The DTCS could perform well across various Chinese cities even under severe hot and moist conditions, with the average annual pPUE consistently below 1.1.

Applied SciencesVol. 15(5)
Wuhan Ship Development & Design Institute (CN), Beihang University (CN), Tsinghua University (CN)
Openalex Percentile: Top 36%
Heat Transfer and Boiling Studies
0.71
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Experimental Study of a Novel Prototype of Dual-Cycle Two-Phase Cooling System for a Data Cabinet — Leixin Wang, Yifan Zhao, et al. · Applied Sciences (2025) | TGRS Research Map | TGRS