Comparative selection of pure and zeotropic refrigerants in cascade heat pumps: Effects on system performance and optimal intermediate temperature

• Identify the best hybrid refrigerant configurations for improved performance. • Develop an optimal T m model using hybrid refrigerant configurations. • Compare the model's T m results with enthalpy methods, within ± 7 % deviation. • Analyze COP from conventional and proposed models, with deviation under ± 3 % . • Apply the FOM model to evaluate COP of cascade HP as a quick and accurate method. This study develops a model to determine the optimal intermediate temperature ( T m , o p t ) that maximises the coefficient of performance (COP) in a typical two-stage cascade heat pump. Focusing on applications requiring simultaneous heating and cooling, the research compares the performance of zeotropic and pure refrigerants in both the high-stage (HS) and low-stage (LS) cycles. It also explores a hybrid configuration where zeotropic refrigerants are used in one stage and pure refrigerants in the other, offering insights into practical design flexibility. A correction factor based on the critical temperature ratio of the working fluids and the condenser temperature on the high-temperature side, the ideal intermediate temperature is found to differ from the mean of the condensing and evaporating temperatures. The model incorporates this adjustment factor to estimate T m , o p t for various refrigerant combinations. The model evaluates performance across a range of operating conditions, with LS evaporating temperatures between 5°C and 15°C and HS condensing temperatures between 65°C and 95°C. Quantitative results demonstrate that the model achieves deviations of less than ±7% for T m , o p t , ±3% for COPs, and under 5.5% for the extended Figure of Merit (FOM) compared with the enthalpy method, confirming its accuracy. The study's novelty lies in integrating correction factors for zeotropic refrigerants and extending the FOM model to hybrid two-stage configurations, confirming its accuracy. The study provides a foundation for improving the energy efficiency and adaptability of cascade heat pump systems, suitable for diverse industrial and residential applications requiring simultaneous heating and cooling.

Authors

Institutions

Publication Details

Journal
Results in Engineering
Published
2025-02-18
DOI
https://doi.org/10.1016/j.rineng.2025.104406
Citations
5
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
3.57
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Comparative selection of pure and zeotropic refrigerants in cascade heat pumps: Effects on system performance and optimal intermediate temperature

Wirote Ritthong, Sokleng Srou, Pongthep Poungthong
5 citations
Results in Engineering
Refrigeration and Air Conditioning Technologies
3.57
article

Comparative selection of pure and zeotropic refrigerants in cascade heat pumps: Effects on system performance and optimal intermediate temperature

Wirote Ritthong, Sokleng Srou, Pongthep Poungthong
article en
5 citations

Abstract

• Identify the best hybrid refrigerant configurations for improved performance. • Develop an optimal T m model using hybrid refrigerant configurations. • Compare the model's T m results with enthalpy methods, within ± 7 % deviation. • Analyze COP from conventional and proposed models, with deviation under ± 3 % . • Apply the FOM model to evaluate COP of cascade HP as a quick and accurate method. This study develops a model to determine the optimal intermediate temperature ( T m , o p t ) that maximises the coefficient of performance (COP) in a typical two-stage cascade heat pump. Focusing on applications requiring simultaneous heating and cooling, the research compares the performance of zeotropic and pure refrigerants in both the high-stage (HS) and low-stage (LS) cycles. It also explores a hybrid configuration where zeotropic refrigerants are used in one stage and pure refrigerants in the other, offering insights into practical design flexibility. A correction factor based on the critical temperature ratio of the working fluids and the condenser temperature on the high-temperature side, the ideal intermediate temperature is found to differ from the mean of the condensing and evaporating temperatures. The model incorporates this adjustment factor to estimate T m , o p t for various refrigerant combinations. The model evaluates performance across a range of operating conditions, with LS evaporating temperatures between 5°C and 15°C and HS condensing temperatures between 65°C and 95°C. Quantitative results demonstrate that the model achieves deviations of less than ±7% for T m , o p t , ±3% for COPs, and under 5.5% for the extended Figure of Merit (FOM) compared with the enthalpy method, confirming its accuracy. The study's novelty lies in integrating correction factors for zeotropic refrigerants and extending the FOM model to hybrid two-stage configurations, confirming its accuracy. The study provides a foundation for improving the energy efficiency and adaptability of cascade heat pump systems, suitable for diverse industrial and residential applications requiring simultaneous heating and cooling.

Results in EngineeringVol. 25
Shinawatra University (TH)
Affordable and clean energy
Openalex Percentile: Top 8%
Refrigeration and Air Conditioning Technologies
3.57
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.