Research on the Diffusion and Deposition Characteristics of Refrigerant Under Vertical Upward Leakage in a Confined Space

In a confined space, the flammability of alternative refrigerants (such as R717, R290, R32, and R1234yf) poses significant safety risks during leaks. However, in the actual refrigeration systems, the direction of refrigerant leakage is difficult to predict, complicating explosion risk assessment. In this work, R717, R290, R32, and R1234yf were selected as the research objects to analyze the diffusion process and deposition characteristics of different refrigerants leaking vertically upward into a confined space, and to explore the migration characteristics of flammable refrigerants under different leakage amounts and flammability area in a confined space. The results show that after vertical upward leakage, the refrigerants tend to impact the top wall and then move along the top wall away from the leak source. High-density refrigerants diffuse primarily near the floor, while less dense refrigerant diffuses along the top and side wall of the space. After the refrigerant leakage stops, R1234yf, with the highest density, exhibited the most pronounced deposition, with the highest concentration near the floor and the lowest at the top (1.69% and 0.7%, respectively). Conversely, lower-density refrigerants showed decreasing floor concentrations and increasing top concentrations, with reduced overall deposition. Compared to the deposition concentration of R290 at the bottom of the room (1.32%), R744 demonstrated higher deposition near the floor than R290, likely due to its higher viscosity at similar densities. In addition, using R290 as an example, the study reveals that the increase in leakage amount and the prolonged time result in a gradual expansion and upward diffusion of the flammability area, encompassing the top of the space, walls, and floor.

Authors

Institutions

Publication Details

Journal
Applied Sciences
Published
2025-02-12
DOI
https://doi.org/10.3390/app15041918
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on the Diffusion and Deposition Characteristics of Refrigerant Under Vertical Upward Leakage in a Confined Space

Xiaohong Han, Yalun Li, Ning Jiang, Peixu Zhou et al.
Applied Sciences
Refrigeration and Air Conditioning Technologies
article

Research on the Diffusion and Deposition Characteristics of Refrigerant Under Vertical Upward Leakage in a Confined Space

Xiaohong Han, Yalun Li, Ning Jiang, Peixu Zhou, Yongjie Lu, Xuan Zhou, Yongjun Ling
article en

Abstract

In a confined space, the flammability of alternative refrigerants (such as R717, R290, R32, and R1234yf) poses significant safety risks during leaks. However, in the actual refrigeration systems, the direction of refrigerant leakage is difficult to predict, complicating explosion risk assessment. In this work, R717, R290, R32, and R1234yf were selected as the research objects to analyze the diffusion process and deposition characteristics of different refrigerants leaking vertically upward into a confined space, and to explore the migration characteristics of flammable refrigerants under different leakage amounts and flammability area in a confined space. The results show that after vertical upward leakage, the refrigerants tend to impact the top wall and then move along the top wall away from the leak source. High-density refrigerants diffuse primarily near the floor, while less dense refrigerant diffuses along the top and side wall of the space. After the refrigerant leakage stops, R1234yf, with the highest density, exhibited the most pronounced deposition, with the highest concentration near the floor and the lowest at the top (1.69% and 0.7%, respectively). Conversely, lower-density refrigerants showed decreasing floor concentrations and increasing top concentrations, with reduced overall deposition. Compared to the deposition concentration of R290 at the bottom of the room (1.32%), R744 demonstrated higher deposition near the floor than R290, likely due to its higher viscosity at similar densities. In addition, using R290 as an example, the study reveals that the increase in leakage amount and the prolonged time result in a gradual expansion and upward diffusion of the flammability area, encompassing the top of the space, walls, and floor.

Applied SciencesVol. 15(4)
Zhejiang University (CN)
National Natural Science Foundation of China
Openalex Percentile: Top 98%
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.