Research on short-circuit fault identification method of traction transformer
The short-circuit fault of traction transformer is very harmful. Aiming at the limitation of the existing second harmonic blocking principle, a differential protection algorithm of traction transformer based on fractal correlation dimension is proposed. The algorithm is sensitive to the important parameters of the nonlinear dynamic evolution characteristics of the transformer. The inrush current and the short-circuit fault current are effectively identified by the different fault dimension eigenvalues of the transformer under different working conditions. The simulation model of $V / x$ traction transformer and fractal protection algorithm is built, and the accuracy of the method is verified by uploading it to the real-time digital simulation platform RT-plus.