Optimization Study of Breaker Failure and Dead zone Protection in Two-thirds Wiring Mode

Aiming at the problem that 450ms is needed to isolate the AC system breaker failure and dead zone fault in the extra-high voltage AC/DC hybrid system, which may lead to the multiple consecutive commutation failure in the multi-circuit DC system and thus seriously threaten the stability of the system, the composition of the isolation time of the AC system breaker failure and dead zone fault in the existing 3/2 breaker is analyzed, and the distributed fast breaker failure and dead zone protection system integrated by string is proposed. By optimizing the breaker failure and dead zone protection logic, simplifying the circuit, shortening the transmission time of the remote trip command and improving the logic of the remote trip protection, and reasonably reducing the redundancy delay of multiple links, the resection time of breaker failure and dead zone faults is shortened from 450ms to 200ms under the premise of guaranteeing the reliability. The simulation and test results show the correctness of the theoretical analysis and the effectiveness of the optimization strategy.

Authors

Publication Details

Published
2024-12-06
DOI
https://doi.org/10.1109/iciba62489.2024.10868704
Primary Topic
Smart Grid and Power Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Optimization Study of Breaker Failure and Dead zone Protection in Two-thirds Wiring Mode

Wan Zhu, Guangwu Dai, Kui Liu, Qingchun Zhao et al.
Smart Grid and Power Systems
article

Optimization Study of Breaker Failure and Dead zone Protection in Two-thirds Wiring Mode

Wan Zhu, Guangwu Dai, Kui Liu, Qingchun Zhao, Longlong Li
article en

Abstract

Aiming at the problem that 450ms is needed to isolate the AC system breaker failure and dead zone fault in the extra-high voltage AC/DC hybrid system, which may lead to the multiple consecutive commutation failure in the multi-circuit DC system and thus seriously threaten the stability of the system, the composition of the isolation time of the AC system breaker failure and dead zone fault in the existing 3/2 breaker is analyzed, and the distributed fast breaker failure and dead zone protection system integrated by string is proposed. By optimizing the breaker failure and dead zone protection logic, simplifying the circuit, shortening the transmission time of the remote trip command and improving the logic of the remote trip protection, and reasonably reducing the redundancy delay of multiple links, the resection time of breaker failure and dead zone faults is shortened from 450ms to 200ms under the premise of guaranteeing the reliability. The simulation and test results show the correctness of the theoretical analysis and the effectiveness of the optimization strategy.

Openalex Percentile: Top 75%
Smart Grid and Power Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.