Impact of Inertia Reduction on Small-Signal Stability and Controllability of Interconnected Synchronous Generators
The integration of renewable energy sources inherently reduces power system inertia, which can result in a higher rate of change of frequency. Moreover, reduced inertia also affects the small-signal stability and controllability of the interconnected synchronous generators (SGs). In this paper, we use the linear state-space model to show the impact of SGs’ inertia constants on eigenvalues, participation factors, and Gramian-based controllability metrics. Both a single-machine and an IEEE 9-bus system were analyzed. The results for the IEEE 9-bus system with three SGs show an optimal range of inertia constants to increase the damping of a specific mode and increase controllability. Thus, a framework for multi-objective optimization combining large-signal stability, small-signal stability, and controllability is proposed that can be applied to grid-forming converters.
Authors
- Boštjan Polajžer (ORCID: https://orcid.org/0000-0001-5022-7391)
- Jožef Ritonja (ORCID: https://orcid.org/0000-0002-3677-8100)
- Antonija Šumiga
Institutions
- University of Maribor (SI)
Publication Details
- Published
- 2024-10-14
- DOI
- https://doi.org/10.1109/isgteurope62998.2024.10863236
- Citations
- 1
- Primary Topic
- Power Systems and Renewable Energy
- Type
- article
- Field-Weighted Citation Impact
- 0.17