Improving ice plant efficiency with Al2O3 nanoparticles and evaporative cooling techniques
Abstract This study focuses on reducing energy consumption in vapor compression refrigeration-based ice plants by incorporating nanoparticle in secondary refrigerants and evaporative cooling technique. Experimental evaluations were performed on a test rig using brine and ethylene glycol as secondary refrigerants. Results showed that brine outperformed glycol, reducing ice formation time by 15% when combined with evaporative cooling. Further enhancement was achieved by incorporating Al 2 O 3 nanoparticles into the brine, which, combined with direct evaporative cooling, reduced ice formation time by 20% compared to glycol. The improved system demonstrated significant performance gains, lowering energy costs and enhancing the Coefficient of Performance (COP).
Authors
- Umesh Gurnani
- Nitin S. Aher
- Anurag Hamilton
- Laxmikant S. Dhamande
- Rakhi Bornare
Institutions
- University of Engineering & Management (IN)
- Hindu College of Pharmacy (IN)
Publication Details
- Journal
- International Journal of Air-Conditioning and Refrigeration
- Published
- 2025-02-05
- DOI
- https://doi.org/10.1007/s44189-025-00069-z
- Citations
- 4
- Primary Topic
- Adsorption and Cooling Systems
- Type
- article
- Field-Weighted Citation Impact
- 2.85