Simulation Analysis and Treatment of Main Transformer Fault in a Hydropower Station

The present paper, based on a hydropower station with an outgoing voltage of 220 kV, examines the situation where a main transformer tripped due to a lightning surge overvoltage, resulting in the burnout of the windings near the transformer's neutral point. Utilizing the electromagnetic transient simulation software ATP-EMTP, initial and oscillating potential distribution equivalent circuit models of the transformer windings were constructed. An excitation source was added to the model's terminal, This analysis aimed to explore the initial potential, and oscillating potential distribution between the transformer's windings under two scenarios: neutral point gap breakdown and neutral point gap intact, and to discuss the causes of internal faults within the transformer. Furthermore, a comprehensive electromagnetic transient simulation model was established, encompassing the 220 kV GIS substation, transmission towers, power lines, generators, and transformers, to simulate and analyze several typical conditions that could lead to internal faults in the transformer. Additionally, preventive measures were proposed to prevent similar faults from occurring in the main transformer in the future.

Authors

Institutions

Publication Details

Published
2024-12-13
DOI
https://doi.org/10.1109/icpes63746.2024.10856623
Citations
1
Primary Topic
Power Systems and Technologies
Type
article
Field-Weighted Citation Impact
0.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Simulation Analysis and Treatment of Main Transformer Fault in a Hydropower Station

Peng Yu, Yi He, Dan Yu, Ding Kuang
1 citations
Power Systems and Technologies
0.21
article

Simulation Analysis and Treatment of Main Transformer Fault in a Hydropower Station

Peng Yu, Yi He, Dan Yu, Ding Kuang
article en
1 citations

Abstract

The present paper, based on a hydropower station with an outgoing voltage of 220 kV, examines the situation where a main transformer tripped due to a lightning surge overvoltage, resulting in the burnout of the windings near the transformer's neutral point. Utilizing the electromagnetic transient simulation software ATP-EMTP, initial and oscillating potential distribution equivalent circuit models of the transformer windings were constructed. An excitation source was added to the model's terminal, This analysis aimed to explore the initial potential, and oscillating potential distribution between the transformer's windings under two scenarios: neutral point gap breakdown and neutral point gap intact, and to discuss the causes of internal faults within the transformer. Furthermore, a comprehensive electromagnetic transient simulation model was established, encompassing the 220 kV GIS substation, transmission towers, power lines, generators, and transformers, to simulate and analyze several typical conditions that could lead to internal faults in the transformer. Additionally, preventive measures were proposed to prevent similar faults from occurring in the main transformer in the future.

Chengdu Medical College (CN)
Openalex Percentile: Top 44%
Power Systems and Technologies
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.