Potential Energy Savings for Three Daily Load Profiles Through Reduced Distribution Transformer Losses
In this work, daily energy losses were calculated for a $13,2 / 0,4 \mathrm{kV} / \mathrm{kV}$, Dy11, $50 \mathrm{~Hz}, 100-\mathrm{kVA}$ distribution transformer using three different load profiles based on real measurements. One of the profiles was also applied to a 400kVA transformer. The calculations were performed for a traditional transformer as per Argentinian standard IRAM 2250 and for two high-efficiency versions, their losses being proposed based on feasible literature alternatives. High efficiency version 1 for each transformer features lower no-load losses and the same total losses; in version 2, both no-load and load losses are reduced. The apparent and active power measurements were made on a university campus with a focus on evening classes; on a company with mixed manufacturing and commercial activities; and on a continuous operation manufacturing plant. The results provide a hint as to the actual savings on transformer energy losses for such realistic daily load profiles, which is key to orient further studies regarding the incorporation of high-efficiency distribution transformers in the Argentinian market.