Determining Moisture Condition of External Thermal Insulation Composite System (ETICS) of an Existing Building

ETICS is a popular external wall insulation system, which is not without possible defects and damages. A frequent cause, direct or indirect, of damage to buildings is the impact of water (moisture). This article presents, among others, the results of tests of the moisture content of ETICS layers, the water absorption and capillary absorption of the render by means of the Karsten tube method, numerical thermo-moisture simulations, and tests of interlayer adhesion, in sample residential buildings. Mass moisture content testing of the wall substrate showed acceptable moisture levels (1-4%m) within masonry walls made of silicate blocks, as well as locally elevated moisture levels (4-8%m) in the case of reinforced concrete walls. Moisture testing of the insulation samples showed a predominantly dry condition, and testing of the reinforcement layer showed an acceptable level of moisture. Severe moisture was found in the sample taken in the ground-floor zone at the interface between mineral wool and EPS-P insulation underneath the reinforced layer. Capillary water absorption tests helped classify silicone render as an impermeable and surface hydrophobic coating. Tests of the water absorption of the facade plaster showed that the value declared by the manufacturer (<0.5 kg/m<sup>2</sup>) was mostly met (not in the ground-floor zone). The simulation calculations gave information that there was no continuous increase in condensation during the assumed analysis time (the influence of interstitial condensation on the observed anomalies was excluded). The tests carried out indicated the occurrence of numerous errors in the implementation of insulation works affecting the moisture content and durability of external partitions.

Authors

Institutions

Publication Details

Journal
Materials
Published
2025-01-29
DOI
https://doi.org/10.3390/ma18030614
Citations
4
Primary Topic
Hygrothermal properties of building materials
Type
article
Field-Weighted Citation Impact
3.02
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Determining Moisture Condition of External Thermal Insulation Composite System (ETICS) of an Existing Building

Paweł Krause, Iwona Pokorska-Silva, Łukasz Kosobucki
4 citations
Materials
Hygrothermal properties of building materials
3.02
article

Determining Moisture Condition of External Thermal Insulation Composite System (ETICS) of an Existing Building

Paweł Krause, Iwona Pokorska-Silva, Łukasz Kosobucki
article en
4 citations

Abstract

ETICS is a popular external wall insulation system, which is not without possible defects and damages. A frequent cause, direct or indirect, of damage to buildings is the impact of water (moisture). This article presents, among others, the results of tests of the moisture content of ETICS layers, the water absorption and capillary absorption of the render by means of the Karsten tube method, numerical thermo-moisture simulations, and tests of interlayer adhesion, in sample residential buildings. Mass moisture content testing of the wall substrate showed acceptable moisture levels (1-4%m) within masonry walls made of silicate blocks, as well as locally elevated moisture levels (4-8%m) in the case of reinforced concrete walls. Moisture testing of the insulation samples showed a predominantly dry condition, and testing of the reinforcement layer showed an acceptable level of moisture. Severe moisture was found in the sample taken in the ground-floor zone at the interface between mineral wool and EPS-P insulation underneath the reinforced layer. Capillary water absorption tests helped classify silicone render as an impermeable and surface hydrophobic coating. Tests of the water absorption of the facade plaster showed that the value declared by the manufacturer (<0.5 kg/m<sup>2</sup>) was mostly met (not in the ground-floor zone). The simulation calculations gave information that there was no continuous increase in condensation during the assumed analysis time (the influence of interstitial condensation on the observed anomalies was excluded). The tests carried out indicated the occurrence of numerous errors in the implementation of insulation works affecting the moisture content and durability of external partitions.

MaterialsVol. 18(3)
Silesian University of Technology (PL)
Sustainable cities and communities
Openalex Percentile: Top 11%
Hygrothermal properties of building materials
3.02
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.