Suitable Grounding Transformer Placement and Vector Group Compensation Matrices for Enhanced Autotransformer Differential Protection

Autotransformers, in which the primary and secondary windings share a part of the same winding, are essential for transmitting large amounts of electrical power and thus require dependable fault protection to ensure network stability. Typically, autotransformers use a star-star-delta configuration, with the delta winding grounded through a grounding transformer to provide a fault path that can be detected by a differential relay. This paper aims to enhance autotransformer differential protection by determining the suitable location for the grounding transformer, whether inside or outside the differential protection boundary, and by selecting the appropriate vector group compensation matrix for each winding to detect faults in the delta winding effectively. MATLAB/SIMULINK is used to simulate a practical power system with an autotransformer and differential relays from two manufacturers to identify these selections. The results demonstrate that placing the grounding transformer outside the differential protection boundary, combined with selecting the delta winding as a reference, provides the best fault detection performance.

Authors

Institutions

Publication Details

Published
2024-12-17
DOI
https://doi.org/10.1109/mepcon63025.2024.10850000
Citations
1
Primary Topic
Fault Detection and Control Systems
Type
article
Field-Weighted Citation Impact
0.33
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Suitable Grounding Transformer Placement and Vector Group Compensation Matrices for Enhanced Autotransformer Differential Protection

Almoataz Y. Abdelaziz, Ahmed S. Sayed, Ehab M. Nabil
1 citations
Fault Detection and Control Systems
0.33
article

Suitable Grounding Transformer Placement and Vector Group Compensation Matrices for Enhanced Autotransformer Differential Protection

Almoataz Y. Abdelaziz, Ahmed S. Sayed, Ehab M. Nabil
article en
1 citations

Abstract

Autotransformers, in which the primary and secondary windings share a part of the same winding, are essential for transmitting large amounts of electrical power and thus require dependable fault protection to ensure network stability. Typically, autotransformers use a star-star-delta configuration, with the delta winding grounded through a grounding transformer to provide a fault path that can be detected by a differential relay. This paper aims to enhance autotransformer differential protection by determining the suitable location for the grounding transformer, whether inside or outside the differential protection boundary, and by selecting the appropriate vector group compensation matrix for each winding to detect faults in the delta winding effectively. MATLAB/SIMULINK is used to simulate a practical power system with an autotransformer and differential relays from two manufacturers to identify these selections. The results demonstrate that placing the grounding transformer outside the differential protection boundary, combined with selecting the delta winding as a reference, provides the best fault detection performance.

Ain Shams University (EG), Higher Institute of Engineering (EG)
Affordable and clean energy
Openalex Percentile: Top 37%
Fault Detection and Control Systems
0.33
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.