Evaluasi Uprating Transformator Distribusi 20 KV pada Penyulang Kelinci di PT. PLN (Persero) ULP Rumbai

The need for electrical energy affects the loading of the transformer which can result in overloading of more than 80%. PLN Standard No. 50 of 1997 states that a transformer is said to be overloaded if the load is more than 80%. This research aims to determine the effect of loading on transformer efficiency and voltage drop on distribution transformers. For loading on transformers before uprating, the results were 92.143%. The voltage drop percentage value obtained for each phase R, S, T is 11.121%, voltage drop percentage on the R phase, 10.973% voltage drop percentage on the S phase, 10.167% voltage drop percentage on the T phase. Uprating was carried out on the transformer to reduce overloading. After the uprating was carried out, the loading results were 55.568 % , which was in accordance with the permitted loading standards. The voltage drop percentage value obtained for each phase R, S, T is 10.973%, voltage drop percentage on the R phase, 10.524 % voltage drop percentage on the S phase, 9.637 % voltage drop percentage on the T phase.

Authors

Institutions

Publication Details

Journal
Jurnal Surya Teknika
Published
2024-12-31
DOI
https://doi.org/10.37859/jst.v11i2.7907
Primary Topic
Belt Conveyor Systems Engineering
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluasi Uprating Transformator Distribusi 20 KV pada Penyulang Kelinci di PT. PLN (Persero) ULP Rumbai

Monice Monice, Usaha Situmeang, Agung Pangestu
Jurnal Surya Teknika
Belt Conveyor Systems Engineering
article

Evaluasi Uprating Transformator Distribusi 20 KV pada Penyulang Kelinci di PT. PLN (Persero) ULP Rumbai

Monice Monice, Usaha Situmeang, Agung Pangestu
article en

Abstract

The need for electrical energy affects the loading of the transformer which can result in overloading of more than 80%. PLN Standard No. 50 of 1997 states that a transformer is said to be overloaded if the load is more than 80%. This research aims to determine the effect of loading on transformer efficiency and voltage drop on distribution transformers. For loading on transformers before uprating, the results were 92.143%. The voltage drop percentage value obtained for each phase R, S, T is 11.121%, voltage drop percentage on the R phase, 10.973% voltage drop percentage on the S phase, 10.167% voltage drop percentage on the T phase. Uprating was carried out on the transformer to reduce overloading. After the uprating was carried out, the loading results were 55.568 % , which was in accordance with the permitted loading standards. The voltage drop percentage value obtained for each phase R, S, T is 10.973%, voltage drop percentage on the R phase, 10.524 % voltage drop percentage on the S phase, 9.637 % voltage drop percentage on the T phase.

Jurnal Surya TeknikaVol. 11(2)
Universitas Lancang Kuning (ID)
Openalex Percentile: Top 74%
Belt Conveyor Systems Engineering
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Evaluasi Uprating Transformator Distribusi 20 KV pada Penyulang Kelinci di PT. PLN (Persero) ULP Rumbai — Monice Monice, Usaha Situmeang, et al. · Jurnal Surya Teknika (2024) | TGRS Research Map | TGRS