Enhanced constant extinction angle control for subsequent commutation failure in LCC‐HVDC

Abstract To mitigate subsequent commutation failure (SCF) in line‐commutated converter‐based high‐voltage direct current transmission systems, the response and limitations of the control system are analysed. The results reveal that due to the prolonged negative deviation of the extinction angle during recovery, the integral output of the proportional–integral controller in constant extinction angle (CEA) significantly reduces the advanced firing angle order, even below normal operating angle. This directly leads to a delayed transition between control strategies and diminishes the effectiveness of CEA. Furthermore, the influence of fault severity, fault type, and AC system strength on SCF is examined. Based on these findings, an enhanced CEA control method to suppress SCF is proposed. By setting an expected firing angle and adaptively adjusting the integral parameter, the control strategy switching moment can be advanced, improving the CEA's control margin and enhancing capability. Moreover, introducing a notch filter reduces firing angle fluctuations and strengthens CEA's ability to suppress SCF. Finally, the theoretical analysis and the effectiveness of the proposed optimization method are validated.

Authors

Institutions

Publication Details

Journal
IET Generation Transmission & Distribution
Published
2025-01-01
DOI
https://doi.org/10.1049/gtd2.13356
Citations
2
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
1.46

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Enhanced constant extinction angle control for subsequent commutation failure in LCC‐HVDC

Baoming Ge, Hao Li, Xiaohua Li, Xiaoyu Sun
2 citations
IET Generation Transmission & Distribution
HVDC Systems and Fault Protection
1.46
article

Enhanced constant extinction angle control for subsequent commutation failure in LCC‐HVDC

Baoming Ge, Hao Li, Xiaohua Li, Xiaoyu Sun
article en
2 citations

Abstract

Abstract To mitigate subsequent commutation failure (SCF) in line‐commutated converter‐based high‐voltage direct current transmission systems, the response and limitations of the control system are analysed. The results reveal that due to the prolonged negative deviation of the extinction angle during recovery, the integral output of the proportional–integral controller in constant extinction angle (CEA) significantly reduces the advanced firing angle order, even below normal operating angle. This directly leads to a delayed transition between control strategies and diminishes the effectiveness of CEA. Furthermore, the influence of fault severity, fault type, and AC system strength on SCF is examined. Based on these findings, an enhanced CEA control method to suppress SCF is proposed. By setting an expected firing angle and adaptively adjusting the integral parameter, the control strategy switching moment can be advanced, improving the CEA's control margin and enhancing capability. Moreover, introducing a notch filter reduces firing angle fluctuations and strengthens CEA's ability to suppress SCF. Finally, the theoretical analysis and the effectiveness of the proposed optimization method are validated.

IET Generation Transmission & DistributionVol. 19(1)
South China University of Technology (CN)
National Natural Science Foundation of China
Openalex Percentile: Top 20%
HVDC Systems and Fault Protection
1.46
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.