Influence of Inrush Current of Converter Transformer on High-voltage DC System Based on Unbalanced Residual Magnetism

In high-voltage direct current (HVDC) transmission systems, the inrush current of the converter transformer can have severe impacts on the system. This paper establishes a model of an ±800kV DC transmission system based on the imbalanced remanence characteristics of the converter transformer. It calculates and analyzes the effects of inrush current on the primary side of the converter transformer and the AC bus. A comparative analysis is conducted between the inrush current under imbalanced and balanced residual magnetism, examining the inrush current characteristics through the content of the inrush current and the proportion of total harmonics under different types and levels of remanence. Finally, the paper compares and analyzes the suppression effects of two closing strategies on the inrush current caused by remanence. The research presented in this paper provides certain guiding significance for comprehensively understanding the impact of residual magnetism in the converter transformer core on inrush current, as well as the impact of inrush current on AC systems.

Authors

Institutions

Publication Details

Published
2024-10-25
DOI
https://doi.org/10.1109/sges63808.2024.10824094
Citations
1
Primary Topic
Electric Power Systems and Control
Type
article
Field-Weighted Citation Impact
0.21

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Influence of Inrush Current of Converter Transformer on High-voltage DC System Based on Unbalanced Residual Magnetism

Xiaoliang Zhuang, Ran Deng, Liangchuang Li, Chenguang Wang et al.
1 citations
Electric Power Systems and Control
0.21
article

Influence of Inrush Current of Converter Transformer on High-voltage DC System Based on Unbalanced Residual Magnetism

Xiaoliang Zhuang, Ran Deng, Liangchuang Li, Chenguang Wang, Ao Xu, Changan Lu
article en
1 citations

Abstract

In high-voltage direct current (HVDC) transmission systems, the inrush current of the converter transformer can have severe impacts on the system. This paper establishes a model of an ±800kV DC transmission system based on the imbalanced remanence characteristics of the converter transformer. It calculates and analyzes the effects of inrush current on the primary side of the converter transformer and the AC bus. A comparative analysis is conducted between the inrush current under imbalanced and balanced residual magnetism, examining the inrush current characteristics through the content of the inrush current and the proportion of total harmonics under different types and levels of remanence. Finally, the paper compares and analyzes the suppression effects of two closing strategies on the inrush current caused by remanence. The research presented in this paper provides certain guiding significance for comprehensively understanding the impact of residual magnetism in the converter transformer core on inrush current, as well as the impact of inrush current on AC systems.

Harbin University of Science and Technology (CN)
China Southern Power Grid
Affordable and clean energy
Openalex Percentile: Top 44%
Electric Power Systems and Control
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.