Impact of fast frequency response on renewable energy source curtailment and load shedding
System operators in low-inertia power systems often have to curtail renewable energy sources (RES) and employ strict under-frequency load shedding (UFLS) schemes to ensure frequency security after an event leading to loss of generation. This approach limits the maximum RES penetration in a system and results to the loss of load. To tackle these problems, fast frequency response (FFR) schemes can be used to limit the frequency Nadir after a disturbance and decrease the need for RES curtailments and UFLS. This article provides insights on the interaction between the Kinetic Energy (KE), Frequency Containment Reserves (FCR), and Nadir after a disturbance, which are the driving mechanisms leading to RES curtailment. Then, it analyses the impact of FFR on the Nadir and its ability to alleviate RES curtailment problems. The low-inertia, islanded, Cyprus dynamic model is used to quantify the results and showcase the impact on a real system.
Authors
- Petros Aristidou (ORCID: https://orcid.org/0000-0003-4429-0225)
- Antonis L. Lazari (ORCID: https://orcid.org/0000-0002-7630-9632)
- Savvas Panagi (ORCID: https://orcid.org/0009-0008-6057-3392)
- Vrahimis Koutsoloukas
Institutions
- Cyprus University of Technology (CY)
Publication Details
- Journal
- IET conference proceedings.
- Published
- 2025-01-01
- DOI
- https://doi.org/10.1049/icp.2024.2088
- Primary Topic
- Wind Turbine Control Systems
- Type
- article
- Field-Weighted Citation Impact
- 0.00