Impact of neutral conductor sizing on LV networks hosting capacity - a Monte-Carlo analysis

Due to the rapid increase in residential PV capacity, it gets more and more difficult for an LV grid to absorb power at peak hours due to overvoltage issues, causing concerns to DSOs and prosumers who are temporarily unable to inject power into the grid. Monte-Carlo simulations were performed with a parametrized LV feeder model representing typical feeder characteristics in Belgium, in order to notably gain insights on the impact of the feeder cable type on the risk of overvoltage occurrences. The simulations’ outputs highlighted the significant impact of the cable type, with a noteworthy influence of the neutral conductor impedance. The significance of impact of the neutral impedance is directly linked to the significance of the unbalance levels of PV production. The gain in terms of voltage excursion (|Vph-N- Vnom|) reduction can be large for a DSO switching from asymmetrical cables (with reduced neutral cross-section) to symmetrical ones. Voltage excursion reductions of 22 to 32% are typically observed, although much larger reductions have been obtained. The reduction of the risk for overvoltage occurrences ranged from 43 to 74% depending on the asymmetrical/symmetrical cable pairs considered.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-01-01
DOI
https://doi.org/10.1049/icp.2024.2107
Primary Topic
Railway Systems and Energy Efficiency
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Impact of neutral conductor sizing on LV networks hosting capacity - a Monte-Carlo analysis

Quentin Antoine, Kristof Vliegen, Peter Kellens
IET conference proceedings.
Railway Systems and Energy Efficiency
article

Impact of neutral conductor sizing on LV networks hosting capacity - a Monte-Carlo analysis

Quentin Antoine, Kristof Vliegen, Peter Kellens
article en

Abstract

Due to the rapid increase in residential PV capacity, it gets more and more difficult for an LV grid to absorb power at peak hours due to overvoltage issues, causing concerns to DSOs and prosumers who are temporarily unable to inject power into the grid. Monte-Carlo simulations were performed with a parametrized LV feeder model representing typical feeder characteristics in Belgium, in order to notably gain insights on the impact of the feeder cable type on the risk of overvoltage occurrences. The simulations’ outputs highlighted the significant impact of the cable type, with a noteworthy influence of the neutral conductor impedance. The significance of impact of the neutral impedance is directly linked to the significance of the unbalance levels of PV production. The gain in terms of voltage excursion (|Vph-N- Vnom|) reduction can be large for a DSO switching from asymmetrical cables (with reduced neutral cross-section) to symmetrical ones. Voltage excursion reductions of 22 to 32% are typically observed, although much larger reductions have been obtained. The reduction of the risk for overvoltage occurrences ranged from 43 to 74% depending on the asymmetrical/symmetrical cable pairs considered.

IET conference proceedings.Vol. 2024(5)
Fluvius (Belgium) (BE)
Openalex Percentile: Top 100%
Railway Systems and Energy Efficiency
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.