Data-Driven Fault Diagnosis in Water Pipelines Based on Neuro-Fuzzy Zonotopic Kalman Filters
This work presents a data-driven approach for diagnosing sensor faults and leaks in hydraulic pipelines using neuro-fuzzy Zonotopic Kalman Filters (ZKF). The approach involves two key steps: first, identifying the nonlinear pipeline system using an adaptive neuro-fuzzy inference system (ANFIS), resulting in a set of Takagi–Sugeno fuzzy models derived from pressure and flow data, and second, implementing a neuro-fuzzy ZKF bench to detect pipeline leaks and sensor faults with adaptive thresholds. The learning phase of the neuro-fuzzy systems considers only fault-free data. Fault isolation is achieved by comparing zonotopic sets and evaluating a fault signature matrix. The method accounts for parametric uncertainty and measurement noise, ensuring robustness. Experimental validation on a hydraulic pipeline demonstrated high precision (up to 99.24%), recall (up to 99.20%), and low false positive rates (as low as 0.76%) across various fault scenarios and operational points.
Authors
- Esvan-Jesús Pérez-Pérez (ORCID: https://orcid.org/0000-0003-2117-3261)
- Julio-Alberto Guzmán-Rabasa (ORCID: https://orcid.org/0000-0002-2104-6345)
- José Armando Fragoso-Mandujano (ORCID: https://orcid.org/0000-0003-0612-2888)
- Yair González-Baldizón (ORCID: https://orcid.org/0000-0001-8524-1724)
- Ildeberto Santos‐Ruiz (ORCID: https://orcid.org/0000-0003-3995-8091)
Institutions
- Tuxtla Gutierrez Institute of Technology (MX)
- Tecnológico Nacional de México (MX)
- Instituto Tecnológico de Hermosillo (MX)
- Universidad Autónoma de Chiapas (MX)
- Universitat Politècnica de Catalunya (ES)
Publication Details
- Journal
- Mathematical and Computational Applications
- Published
- 2024-12-30
- DOI
- https://doi.org/10.3390/mca30010002
- Citations
- 2
- Primary Topic
- Fault Detection and Control Systems
- Type
- article
- Field-Weighted Citation Impact
- 0.66
Funders
- Tecnológico Nacional de México