Lightning protection of the 110 kV substation at the wind park Ivan Sedlo against transients caused by direct lightning strikes into connected overhead line

This paper deals with the lightning protection of 110 kV substation at the wind park Ivan Sedlo against transients caused by direct lightning strikes into connected 110 kV overhead line. Lightning protection level (LPL) I as per standard IEC 62305-1 is selected for this substation to reduce probability of equipment failure to low level. Calculations are done in the EMTP-ATP software. Three critical scenarios are analysed: shielding failure at the connected 110 kV overhead line, lightning strike to the top of first tower in front of the substation and lightning strike to the top of gantry tower at the entrance to the substation. It is presented that LPL I for analysed configuration of substation can be achieved by installing two sets of surge arresters. First set of surge arresters is installed in the transmission line bay, while second set of surge arresters is installed in the transformer bay. Transferred lightning transients through the power transformer are also calculated. It is presented that one additional set of surge arresters is necessary at the 30 kV side of the power transformer, to protected it against transferred lightning transients. Energy duty of all three sets of surge arresters is calculated. At the 110 kV voltage level energy stress of surge arresters is significant and strongly depends on the substation grounding resistance value. Estimated energy stress of set of surge arresters at the 30 kV voltage level is very low.

Authors

Institutions

Publication Details

Journal
IJEEC - INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTING
Published
2024-12-10
DOI
https://doi.org/10.7251/ijeec2402043b
Citations
1
Primary Topic
Lightning and Electromagnetic Phenomena
Type
article
Field-Weighted Citation Impact
0.33
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Lightning protection of the 110 kV substation at the wind park Ivan Sedlo against transients caused by direct lightning strikes into connected overhead line

Mladen Banjanin, Velibor Crnovčić, Mihael Tomšič
1 citations
IJEEC - INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTING
Lightning and Electromagnetic Phenomena
0.33
article

Lightning protection of the 110 kV substation at the wind park Ivan Sedlo against transients caused by direct lightning strikes into connected overhead line

Mladen Banjanin, Velibor Crnovčić, Mihael Tomšič
article en
1 citations

Abstract

This paper deals with the lightning protection of 110 kV substation at the wind park Ivan Sedlo against transients caused by direct lightning strikes into connected 110 kV overhead line. Lightning protection level (LPL) I as per standard IEC 62305-1 is selected for this substation to reduce probability of equipment failure to low level. Calculations are done in the EMTP-ATP software. Three critical scenarios are analysed: shielding failure at the connected 110 kV overhead line, lightning strike to the top of first tower in front of the substation and lightning strike to the top of gantry tower at the entrance to the substation. It is presented that LPL I for analysed configuration of substation can be achieved by installing two sets of surge arresters. First set of surge arresters is installed in the transmission line bay, while second set of surge arresters is installed in the transformer bay. Transferred lightning transients through the power transformer are also calculated. It is presented that one additional set of surge arresters is necessary at the 30 kV side of the power transformer, to protected it against transferred lightning transients. Energy duty of all three sets of surge arresters is calculated. At the 110 kV voltage level energy stress of surge arresters is significant and strongly depends on the substation grounding resistance value. Estimated energy stress of set of surge arresters at the 30 kV voltage level is very low.

IJEEC - INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTINGVol. 8(2)
University of Banja Luka (BA), University of East Sarajevo (BA), Ministry of the Interior (SI)
Affordable and clean energy
Openalex Percentile: Top 32%
Lightning and Electromagnetic Phenomena
0.33
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Lightning protection of the 110 kV substation at the wind park Ivan Sedlo against transients caused by direct lightning strikes into connected overhead line — Mladen Banjanin, Velibor Crnovčić, et al. · IJEEC - INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTING (2024) | TGRS Research Map | TGRS