Application of PDC Testing for Medium-Voltage XLPE Cable Joint Water Ingress Detection

This article took 6.6-kV medium-voltage crosslinked polyethylene (XLPE) cables as the test object, conducting field tests of polarization and depolarization currents (PDCs), very-low-frequency (VLF) tan <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$\delta $ </tex-math></inline-formula>, and time-domain reflectometry (TDR). The correlation between PDC testing and VLF tan <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$\delta $ </tex-math></inline-formula> and TDR measurements was investigated to enhance the effectiveness of the PDC testing method. PDC test outcomes indicated that polarization currents sometimes exhibit increasing or non monotonic trends over time, referred to as abnormal trends herein. Through in-depth research combining TDR measurement results and relevant theoretical frameworks, it is confirmed that abnormal polarization currents are attributable to water ingress issues in cable joints. Water ingress into the joint induces nonlinear variations in insulation conductivity with the electric field, manifesting as abnormal trends in polarization currents at the joint-insulation interface. These kinds of abnormal polarization currents can serve as an effective diagnostic indicator for identifying cable joint issues. Moreover, VLF tan <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$\delta $ </tex-math></inline-formula> measurements alone sometimes fail to accurately diagnose water ingress issues in cable joints, necessitating the use of TDR for further diagnosis.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Dielectrics and Electrical Insulation
Published
2024-12-27
DOI
https://doi.org/10.1109/tdei.2024.3523877
Citations
4
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.47

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Application of PDC Testing for Medium-Voltage XLPE Cable Joint Water Ingress Detection

W. K. Chern, Changyou Suo, Amer M. Y. M. Ghias, Cao Hongyan
4 citations
IEEE Transactions on Dielectrics and Electrical Insulation
High voltage insulation and dielectric phenomena
0.47
article

Application of PDC Testing for Medium-Voltage XLPE Cable Joint Water Ingress Detection

W. K. Chern, Changyou Suo, Amer M. Y. M. Ghias, Cao Hongyan
article en
4 citations

Abstract

This article took 6.6-kV medium-voltage crosslinked polyethylene (XLPE) cables as the test object, conducting field tests of polarization and depolarization currents (PDCs), very-low-frequency (VLF) tan <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$\delta $ </tex-math></inline-formula>, and time-domain reflectometry (TDR). The correlation between PDC testing and VLF tan <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$\delta $ </tex-math></inline-formula> and TDR measurements was investigated to enhance the effectiveness of the PDC testing method. PDC test outcomes indicated that polarization currents sometimes exhibit increasing or non monotonic trends over time, referred to as abnormal trends herein. Through in-depth research combining TDR measurement results and relevant theoretical frameworks, it is confirmed that abnormal polarization currents are attributable to water ingress issues in cable joints. Water ingress into the joint induces nonlinear variations in insulation conductivity with the electric field, manifesting as abnormal trends in polarization currents at the joint-insulation interface. These kinds of abnormal polarization currents can serve as an effective diagnostic indicator for identifying cable joint issues. Moreover, VLF tan <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$\delta $ </tex-math></inline-formula> measurements alone sometimes fail to accurately diagnose water ingress issues in cable joints, necessitating the use of TDR for further diagnosis.

IEEE Transactions on Dielectrics and Electrical InsulationVol. 32(1)
Nanyang Technological University (SG)
National Research Foundation, Nanyang Technological University
Clean water and sanitation
Openalex Percentile: Top 37%
High voltage insulation and dielectric phenomena
0.47
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.