Optimizing economic performances of foundation earth-to-air heat exchangers for low-technology residential air-conditioning

• Economic performance analysis of foundation earth-to-air heat exchanger. • Modeling heating and cooling loads of a house integrated with a geothermal exchanger. • An estimated load reduction of about 700 kWh (4.3%) throughout the year. • Unviable economic performance estimated in Quebec (Canada) due to low energy fare. • 40% of the exchanged heat lost through coupling and short-circuiting. Despite its classification as a low-technology and nearly passive sustainable system, the use of earth-to-air heat exchangers in residential settings remains relatively uncommon, primarily due to the expenses associated with excavation. Nevertheless, positioning the heat exchanger around the building’s foundations during construction offers a potential solution to mitigate these costs. This study conducts an economic viability analysis for such a configuration, focusing on a typical single-family dwelling in Montréal, Canada. A sizing investigation revealed that ducts with relatively small diameters (approximately 20 cm), constructed from cost-effective materials, are optimal. These ducts should be placed as deep and as distant from the foundation as feasible. The optimal heat exchanger configuration reduces the building’s heating/cooling load by 701 kWh per year (4.3 %). However, despite minimal excavation expenses, the economic analysis suggests an unviable Levelized cost of Energy for the province of Quebec (0.182 US$.kWh −1 ) compared to the low electricity rates in the area (a domestic fare of 0.059 US$.kWh −1 ). The findings underscore notable losses attributable to thermal short-circuiting influenced by the basement walls and coupling affected by the mandatory Heat Recovery Ventilation system. Overall, it was determined that only 60 % of the sensible heat exchanged with the soil effectively contributes to load reduction.

Authors

Institutions

Publication Details

Journal
Energy and Buildings
Published
2024-12-27
DOI
https://doi.org/10.1016/j.enbuild.2024.115250
Citations
9
Primary Topic
Geothermal Energy Systems and Applications
Type
article
Field-Weighted Citation Impact
0.92

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Optimizing economic performances of foundation earth-to-air heat exchangers for low-technology residential air-conditioning

Mathieu Patin, Daniel R. Rousse
9 citations
Energy and Buildings
Geothermal Energy Systems and Applications
0.92
article

Optimizing economic performances of foundation earth-to-air heat exchangers for low-technology residential air-conditioning

Mathieu Patin, Daniel R. Rousse
article en
9 citations

Abstract

• Economic performance analysis of foundation earth-to-air heat exchanger. • Modeling heating and cooling loads of a house integrated with a geothermal exchanger. • An estimated load reduction of about 700 kWh (4.3%) throughout the year. • Unviable economic performance estimated in Quebec (Canada) due to low energy fare. • 40% of the exchanged heat lost through coupling and short-circuiting. Despite its classification as a low-technology and nearly passive sustainable system, the use of earth-to-air heat exchangers in residential settings remains relatively uncommon, primarily due to the expenses associated with excavation. Nevertheless, positioning the heat exchanger around the building’s foundations during construction offers a potential solution to mitigate these costs. This study conducts an economic viability analysis for such a configuration, focusing on a typical single-family dwelling in Montréal, Canada. A sizing investigation revealed that ducts with relatively small diameters (approximately 20 cm), constructed from cost-effective materials, are optimal. These ducts should be placed as deep and as distant from the foundation as feasible. The optimal heat exchanger configuration reduces the building’s heating/cooling load by 701 kWh per year (4.3 %). However, despite minimal excavation expenses, the economic analysis suggests an unviable Levelized cost of Energy for the province of Quebec (0.182 US$.kWh −1 ) compared to the low electricity rates in the area (a domestic fare of 0.059 US$.kWh −1 ). The findings underscore notable losses attributable to thermal short-circuiting influenced by the basement walls and coupling affected by the mandatory Heat Recovery Ventilation system. Overall, it was determined that only 60 % of the sensible heat exchanged with the soil effectively contributes to load reduction.

Energy and BuildingsVol. 328
Centre National de la Recherche Scientifique (FR), Université du Québec à Montréal (CA), Franche-Comté Électronique Mécanique Thermique et Optique - Sciences et Technologies (FR), Université de Franche-Comté (FR), École de Technologie Supérieure (CA)
Natural Sciences and Engineering Research Council of Canada
Openalex Percentile: Top 29%
Geothermal Energy Systems and Applications
0.92
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.